Eap 110 annunciator, Mec 2/20 engine controller, Specifications ordering information – Technicolor - Thomson Generator Set Annunciator EAP 110 User Manual

Page 2: External connections

Advertising
background image

THOMSON TECHNOLOGY INC. • 9087A - 198th STREET, LANGLEY, BC CANADA V1M 3B1

TELEPHONE: (604) 888-0110 • FAX: (604) 888-3381 • E-MAIL: [email protected] • www.thomsontechnology.com

SUPPLY VOLTAGE

12V or 24V nominal (

± 20%), negative ground

SUPPLY CURRENT

100 ma (maximum), (

± 20%)

COMMUNICATION PORT

RS 422, 4.8 KBaud, Thomson Technology T-Net Protocol
to MEC 2/MEC 20 8 conductor #22 AWG (min) Shielded/
Twisted cable (1000 ft Max), Plug-in RJ45 Connector

DIGITAL CONTACT INPUT

Close to DC Negative

TEMPERATURE RANGE

-40

° C to +50° C

ENVIRONMENTAL

Faceplate NEMA 12, Rear Enclosure NEMA 1

DIMENSIONS

6.0” W x 6.0” H x 3.0” D

Flush mount adapter option

(7.0” w x 7.0” H)

MOUNTING

Surface Mount (Standard), Flush-mount (Optional) Rear
Enclosure conduit box c/w Qty 8 1/2” knockouts

NOTE: Specifications subject to change without notice.

CL057 REV 0 02/07/01

SPECIFICATIONS

ORDERING INFORMATION

The EAP 110 may be ordered separately or in conjunction with unit mount control panels or engine controllers.
When ordering for use with existing MEC 2/MEC 20 engine controller applications in the field, contact Thomson
Technology for additional information regarding software/hardware compatibility.

The EAP 110 is supplied from the factory with standard alarm labeling for MEC 2* or MEC 20* engine controllers which
are applied to meet NFPA 110 Level 1/NFPA 99 or CSA 282 alarm requirements. The standard EAP 110 can be labeled and
programmed for alternate alarm configurations (consult Thomson Technology for further information). When specified, the
optional flush mount adapter plate is supplied loose with the standard Annunciator for field installation.

BASIC MODEL
MOUNTING

S = SURFACE(Standard)
F = FLUSH(Optional)

EXAMPLE:

EXTERNAL CONNECTIONS

+

O

O

-

O

O

O

O

O

O

Ext1 Ext2 Ext3 Ext4

B+ B-

B+ B-

Communication
Port

1000' maximum cable length

No

Connection

J7

Expansion
Port

GRD

J6

MEC 2/20
Engine
Controller

Communication
Cable**

12-24V Engine
Cranking Battery

External Alarm
Sensing Contacts
(optional use
as required)

** 8 conductor Shielded Twisted Cable c/w RJ45 connectors.

EAP 110
Annunciator

J1

EAP 110 – S

*Note: For MEC 2 / MEC 20 details refer to separate brochures.