Installation, Warning hazardous voltage – Trane WPWD User Manual

Page 10

Advertising
background image

10

WSHP-SVX02A-EN

General Installation Checks
The checklist below is a summary of
the steps required to successfully in-
stall a unit. This checklist is intended to
acquaint the installing personnel with
procedures required in the installation
process. It does not replace the de-
tailed instructions called out in the ap-
plicable sections of this manual.

1 Remove packaging and inspect the

unit. Check the unit for shipping
damage and material shortage; file
a freight claim and notify appropri-
ate sales representation.

Note: The units have been tied to
the skid by (4) angle brackets. Re-
move these brackets from the unit
to slide unit from skid.

2 Verify the correct model, options

and voltage from the unit name-
plate.

3 Verify the installation location of

the unit will provide the required
clearance for proper operation.

4 Remove refrigeration access panel

and inspect the unit. Be certain the
refrigerant tubing has clearance
from adjacent parts.

WARNING

Hazardous

Voltage!

Disconnect all electric power,

including remote disconnects

before servicing. Follow proper

lockout/tagout procedures to

ensure the power can not be

inadvertently energized. Failure to

disconnect power before

servicing could result in death or

serious injury.

Main Electrical

5 Verify the power supply complies

with the unit nameplate specifica-
tions.

6 Inspect all control panel compo-

nents; tighten any loose connec-
tions.

7 Connect properly sized and pro-

tected power supply wiring to a
field-supplied/installed disconnect
switch and to the main power ter-
minal block (1TB1) in the unit con-
trol box for the 20-ton equipment,
or (1K1) for the 2-ton through 6-
ton equipment.

8 Install proper grounding wires to

an earth ground.

Note: All field-installed wiring must
comply with NEC and applicable local
codes.

Low Voltage Wiring (AC & DC)

Requirements
9 Connect properly sized control wir-

ing to the proper termination
points between the field supplied
thermostat and the terminal strip
located in the equipment control
box.

Installation

Advertising
This manual is related to the following products: