Important safety instructions, Save these instructions, Location warnings – Tripp Lite APSINT612 User Manual

Page 3: Battery connection warnings, Equipment connection warnings, Operation warnings

Advertising
background image

3A

Important Safety Instructions

SAVE THESE INSTRUCTIONS!

This manual contains important instructions and warnings that should be followed during the installation, operation and storage of all Tripp Lite
Inverter/Chargers.

Location Warnings

• Install your Inverter/Charger (whether for a mobile or stationary application) in a location or compartment that minimizes exposure to

heat, dust, direct sunlight and moisture.

• Although your Inverter/Charger is moisture resistant, it is NOT waterproof. Flooding the unit with water will cause it to short circuit

and could cause personal injury due to electric shock. Never immerse the unit, and avoid any area where standing water might
accumulate. Mounting should be in the driest location available.

• Leave a minimum of 5 cm (2") clearance at front and back of the Inverter/Charger for proper ventilation. The heavier the load of

connected equipment, the more heat will be generated by the unit.

• Do not install the Inverter/Charger directly near magnetic storage media, as this may result in data corruption.

• Do not install near flammable materials, fuel or chemicals.

Battery Connection Warnings

• The Inverter/Charger will not operate (with or without utility power) until batteries are connected.

• Multiple battery systems must be comprised of batteries of identical voltage, age, amp-hour capacity and type.

• Because explosive hydrogen gas can accumulate near batteries if they are not kept well ventilated, your batteries should not be

installed (whether for a mobile or stationary application) in a “dead air” compartment. Ideally, any compartment would have some
ventilation to outside air.

• Sparks may result during final battery connection. Always observe proper polarity as batteries are connected.

• Do not allow objects to contact the two DC input terminals. Do not short or bridge these terminals together. Serious personal injury

or property damage could result.

Equipment Connection Warnings

Do not use a Tripp Lite APS Inverter/Charger in life support or healthcare applications where a malfunction or failure of a
Tripp Lite APS Inverter/Charger could cause failure of or significantly alter the performance of, a life support device or medical
equipment.

• Do not modify the Inverter/Charger’s plug or receptacle in a way that eliminates its ground connection. Do not use

power adapters that will eliminate the plug’s ground connection.

• Connect your Inverter/Charger only to a properly grounded AC power outlet. Do not plug the unit into itself; this will damage the

device and void your warranty.

• You may experience uneven performance results if you connect a surge suppressor, line conditioner or UPS system to the output of the

Inverter/Charger.

Operation Warnings

• Your Inverter/Charger does not require routine maintenance. Do not open the device for any reason. There are no user serviceable parts

inside.

• Potentially lethal voltages exist within the Inverter/Charger as long as the battery supply and/or AC input are connected. During any

service work, the battery supply and AC input connection should therefore be disconnected.

• Do not connect or disconnect batteries while the Inverter/Charger is operating in either inverting or charging mode. Operating Mode

Switch should be in the OFF position. Dangerous arcing may result.

Advertising