Toshiba RSAP User Manual

Page 3

Advertising
background image

3

Physical Characteristics

Weight: 10lbs
Height: 8 inches
Width: 8 inches
Depth: 4.8 inches

Installation

1. Locate the area where the Remote Status Alarm Panel (RSAP) will be installed.

The monitor should be within 1000 feet from the UPS.

2. Mount the monitor to the wall using the four pre-drilled holes in the back. Use

appropriate hardware for the installation.

3. Wiring requirements are: 7 twisted pair 16 AWG cable run in metal conduit.

Preferred use of Belden Catalog No. 1485 (8 twisted pair) or equivalent. All
electrical and mechanical connections to be made per local and /or national
electric codes.

4. Connect the conduit to the RSAP by punching the appropriately sized hole in a

convenient location.

5. Referring to Figure 2.0, 3.0 and the corresponding UPS wiring diagram, connect

the seven (7) pairs of twisted wire from the RSAP to the customer accessible
alarm contact terminal bar in the UPS module. (Refer to UPS manual for location)

6. Referring to Figure 3.0, install (6) AA batteries. Batteries will provide about

eight (8) hours of run time in the event of an AC power failure. Replace these
batteries yearly for optimum performance.

7. Referring to Figure 1.0, connect the power supply adapter into the corresponding

jack located on the bottom left-hand side of the RSAP enclosure. Plug the power
supply into a convenient 120V/60Hz wall receptacle. Failure to connect to a
suitable wall outlet will drain the RSAP’s internal batteries and/or result in
damage to the monitor. (If supplied with the hardwire version, please refer to
Figure 3.1 for AC input terminal block layout. Connect L1, Neutral, and Ground
with minimum of 18AWG wire.)


*The RSAP must be installed by a qualified electrician. Installation to be inspected by an
Authorized TIC trained Service Engineer at the time of startup.

Advertising