RBC-FDP2-F-PE Interface

Installation and Operating Instructions

Mounting

The FDP2 should be
mounted using the
keyhole mounting
points as indicated in
the adjacent diagram.

The FDP can be
mounted horizontally
or vertically.

Ш 4.00

75.00

Ш 9.00

Basic Cable Installation

Cabling should be a minimum 0.75mm

2

throughout. Terminals TCC-NET

A/B connect to the Toshiba TCC-NET. TCC-NET installation should follow
Toshiba installation specifications. Terminals R1-R2 connect to fault
monitoring or indication equipment according to the specified rating of the
relay. The FDP2 is powered from the TCC-NET and requires no extra power
supply.

TCC-NET

Indoor Unit

To fault monitoring

TCC-NET

D-BUS

RELAY

A

B D1 D2

R1 R2

C

Toshiba Remote Controller

A

B

LED Functionality

Normal Operation

Key:

FLASHING

OFF

ON

R

G

Power-Up sequence
Factory Configuration

R

G

No Fault State

R

G

Power-Up sequence
Custom Configuration

R

G

Unit Fault

R

G

TCC-NET Holdoff. After
power-up and during
unit configuration

Error Conditions

R

G

Device configuration error

R

G

No unit master found on TCC-Net

R

G

D-BUS Communications timeout

R

G

Duplicate D-BUS Address detected

Standard Operation

ON

SW1

SW7

ON

FDP2 Configuration Switches

The FDP2 has a number of standard configurations that can be set using
switches SW1 to SW7 shown above. Factory configuration is configured
with all switches OFF. In this mode the FDP2 operates as a standard fault
monitoring device. Additional preset modes are available using SW1 and
SW2 to operate the system in preset Heat, Cool and Auto modes*.

Fault Monitoring

8 Units max

Fault Monitoring + Locked Cooling Preset

18

8 Units max

Fault Monitoring + Locked Heating Preset

23

8 Units max

Fault Monitoring + Locked Auto Preset

21

8 Units max

*Units that do not support specific modes such as cooling-only units will operate in fan-only in unsupported
modes.

FDP2 Description

The FDP2-F is a monitoring and control interface for the Toshiba Digital
Inverter, SHRM and SMMS range of air-conditioners.

Fault Reporting

The FDP2-F Interface detects all indoor and outdoor faults occurring in
TCC-NET compatible Toshiba air-conditioners and reports them by closing
relay contacts R1-R2. The FDP2-F is connected on the TCC-NET network
with or without a standard remote controller and detects any faults that can
be displayed on the controller for up to 8 units. Red and Green LEDs
Indicate Fault/No Fault state.

Control Functions

GROUP CONTROL. Multiple FDP2 Interfaces can be connected to form
large groups of units controlled from a single remote controller.

OPERATION PRESETS. Remote controller operation can be locked and
various different preset run conditions can be sent from the FDP2.

DUTY/STANDBY. Pairs of FDPs can operate duty/standby control with 24
hour alternating duty, and changeover on fault.

HARDWIRED CONTROL. In conjuntion with an FDP2-BMS unit control can
be achieved through potentiometer and volt-free contact inputs as well as
via BMS integration.

CUSTOM CONTROL. FDP2 interfaces can be supplied in custom
configurations to suit specific applications.

Warnings and Cautions

Do not exceed the specified fault relay ratings

Ø 4.00

26.00

20.00

13.00

18.60

87.00

72.00

ALL DIMENSIONS IN MM

NOT TO SCALE

ON

SW1

SW7

ON

RealTime Control Systems Ltd

FDP2 Model 9410-2-A6

63.00

Fault

No Fault

Fault Interface

FDP2-F

TCC-NET

D-BUS

RELAY

A

B

D1

D2

R1

R2

C

Ш 9.00