Toshiba TOSVERT VF-S11 User Manual

Page 18

Advertising
background image

E6581222

16

■ VF-S11 → Computer

At time of broadcast communication of the binary mode, returning of data is not executed except for
the inverter to be returned (inverter number 00H) and when the inverter number is not matched. This
is because there will be a risk that the returned data may be deformed.

1) Normal processing

1. 2FH “/” (1 byte)

Start code in binary mode

2. INV-NO (1Byte)

Inverter number

00H to 3FH

If the inverter number matches up with that specified from the operation panel, data will
be returned from the inverter. If the inverter number does not match, the data will be
judged invalid and no data will be returned.
Communication data will be invalidated and data will not be returned either if the in-
verter number does not match.

(Inverter number is considered matched if it is omitted

during reception)

3. CMD(1Byte)

:‘Y’ (Block communication command [monitoring])

Lowercase letter ‘y’ during an inverter trip, including standing by for retrying and during
a trip.

4. Number of read data groups (1 byte)

: Return the number of data groups to be read (00H to 05H).

5. Write status (1 byte) : Return 00H to 03H.

* Failing to write in the specified parameter in the number of write data groups, set “1” in
the corresponding bit for the parameter failed to write. (See below.)

6. Read data1 - 5 (2 bytes)

: Return according to the number of read data groups. “0000H” is returned as dummy
data if “0” is selected as a parameter.

Read data1: Data selected by . Read data2: Data selected by .

Read data3: Data selected by . Read data4: Data selected by .

Read data5: Data selected by .

7.SUM(1Byte)

: Checksum (Cannot be omitted) 00H to FFH

Lower two digits (1 byte) of total sum from start code of return data to read data.

■ Example
(When set as follows:  =  (Command 1),  =  (frequency command value),


=  (status), =  (output frequency),  =  (output current),  =  (output voltage) and



=  (alarm)

Computer → Inverter 2F 58 02 05 C4 00 17 70 D9
Inverter → Computer 2F 59 05 03 00 00 00 00 00 00 00 00 00 00 90 (When parameter is not set)
Inverter → Computer 2F 59 05 00 40 00 00 00 00 00 00 00 00 00 CD CD (When parameter is set)
Inverter → Computer 2F 59 05 00 64 00 17 70 1A 8A 24 FD 00 00 3D (During operation at 60Hz)

Start
Code

“ ”

INV

No.

CMD

“Y”

Number
of Read

Data

Groups

Write

Status

Read

data1

high

Read

data1

low

Read

data2

high

Read

data2

low

Read

data3

high

Read

data3

low

Read

data4

high

Read

data4

low

Read

data5

high

Read

data5

low

SUM

Checksum area

Omissible

Number of read data groups x 2 bytes

Bit Position

7

6

5

4

3

2

1

0

Data Type





Advertising