TOA Electronics TM-4500 User Manual

Page 16

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

16

Figure 46

Hearth Extensions and Wall Shields

A hearth extension must be installed with
all fireplaces. It is to protect the combustible
floor in front of the fireplace from both
radiant heat and sparks. The hearth exten-
sion must extend beyond the front at
least 20" (508 mm) and both sides at least
12" (305 mm) (

Figure 47 ). Use a hearth

extension constructed of a durable noncom-
bustible material having an equal or better
(lower k value) insulating value of k = .84
BTU IN/FT

2

HR

°

F or a thermal resistance

that equals or exceeds r = 1.19 HR

°

F FT

2

/

BTU IN. With these values, determine the
minimum thickness/material required using
the formula and

Page 17.

Note: Any noncombustible material whose k
value is less than .84 or whose r value is more
than 1.19 is acceptable.

If the fireplace is installed on a combustible
floor, use the metal safety strips (provided)
on the floor extending half under the fire-
place and half under the hearth extension.

A wall shield is required where a continuous
perpendicular side wall is within 12" of the
fireplace opening (

Figure 48 ). Use a 36" W x

36" H wall shield constructed of a durable,
noncombustible material having an equal or
better (lower k value) insulating value than k =
.54 BTU IN/FT

2

HR

°

F. At no time may a

perpendicular side wall be located closer than
9" from the fireplace opening.

If fireplace is installed diagonally across a 90

°

corner; no wall shields are required.

Fireplace

Opening

Typical Installation

6

⁹⁄₁₆"

(167mm)

12"

(305mm)

Min.

Combustible

Mantel

and Trim

Spacer

Noncombustible

Wall Covering

Finished

Wall

12"

(305mm)

Max.

1

¹⁄₂" (38mm)

Figure 47

A

B

D

C

C

Hearth Extension Dimensions

A

20" (508 mm)

B

36" (914 mm)

C

12" (305 mm)

D

60" (1524 mm)

Methods of Determini

ng Hearth Extension and Wall Shield

Equivalents - To determine the thickness required for the alternate
material when either the “k” value or “r” value is known, use either the
k formula or r formula.

Example: If Micore 160 is to be used for the hearth extension fireplace,
how thick must this material be?

k

M

= k value per inch of

alternate material

r

M

= r value per inch of

alternate material

T

M

= minimum thickness required for

alternate material

T

S

= standard thickness of the

alternate material

k

L

= k value per inch of

listed material

r

L

= r value per inch of

listed material

T

L

= minimum thickness of

listed material

Note: An asterix “*” indicates, it is a value taken from Table 1.
Using the k formula:

Minimum

k-value (per Inch) of

Specified min.

thickness of

=

alternate material (k

M

) x

thickness

alternate

k-value (per inch)

of listed

material (T

M

)

of listed material (k

M

)

material (T

L

)

T

M

(inches)

=

k

M

x

T

L

*.84

T

M

(inches)

=

*.35

x

1"

*.84

.416 (inches) =

.416

x

1"

Answer - The minimum required thickness of the Micore 160 is .417”,
therefore round up to nearest standard thickness available which is 1/2”.

Using the r formula:

Minimum

r-value (per Inch)

Specified min.

thickness of

=

of listed material

x

thickness

alternate

r-value (per inch)

of listed

material

of alternate material

material

T

M

(inches)

=

r

L

x

T

L

r

M

T

M

(inches)

=

*1.19

x

1"

*2.86

.416 (inches)=

.416

x

1"

Advertising