QFNA-IOM-1

Maintenance

Interval

Task

Procedure

Notes

Weekly or
Bi-Weekly

Grease lubricated bearings

(moderate to dirt, dry conditions*)

Apply grease to the inlet and

outlet bearing grease zerks while

the fan is operating. Stop

application when grease is seen

being purged through the bearing

seals. Once the purge level is

determined, use the minimum

amount of grease that is possible

to reach purge (purge = point at

which grease is visually seen

escaping from the bearing seals).

For most ambient temperatures

(0 to 150° F), use a high quality,

all-purpose, Lithium/Lithium

complex based, #2 EP grease

(Mobilith AW-2, Texaco Starplex

2, Shell Alvania #2, or

equivalent). For “extreme”

ambient conditions (less than 0° F

and more than 150° F), a

synthetic or specialty purpose

grease may be considered. For

specific recommendations,

contact your closest Trane

Sales/Service office.

Table 9 - Schedule Maintenance - Q Fan and Super Q II Fan