Toshiba 48-1250 A User Manual

Page 24

Advertising
background image

TD - Series

- 18 -

TD Series

Digital Solid State Soft Starter 48 - 1250A

5.4.4 Kick Start Mode Functions

5.4.5 Decel Mode Functions

5.4.6 Protection Features

Fn

Group

Function

Adjustment

Range

Setting

Increments

Factory

Setting

Section

F025

Deceleration Ramp

0=Disabled / Coast to Stop
1=Enabled (except in event of OL Trip)
2=Enabled (continued Decel on OL Trip)

1

0 (Disabled)

5.5.5

F026

Begin Decel Level (BDL)

0 - 100 %

1%

60%

5.5.5

F027

Decel Shut Off Voltage

0 to (BDL minus 1)%

1%

30%

5.5.5

F028

Decel Ramp Time

1 - 60 Seconds

1 second

10 seconds

5.5.5

F029

Reserved

Reserved

Reserved

Reserved

5.5.5

De

ce

l

M

ode

Fn

Group

Function

Adjustment

Range

Setting

Increments

Factory

Setting

Section

F030

Current Imbalance Trip

0=Disabled
1=Enabled

1

0 (Disabled)

5.5.6

F031

Current Imbalance Trip %

5 - 30%

1%

10%

5.5.6

F032

Current Imbalance Trip Delay

1 - 20 seconds

1 second

2 seconds

5.5.6

F033

Over Current / Shear Pin Trip

0=Disabled
1=Enabled

1

0 (Disabled)

5.5.6

F034

Over Current / Shear Pin Trip %

50 - 300% (note1)

1%

125%

5.5.6

F035

Over Current Trip Delay

1 - 20 seconds

1 second

1 second

5.5.6

F036

Under Current Trip

0=Disabled
1=Enabled

1

0 (Disabled)

5.5.6

F037

Under Current Trip %

10 - 90% (note1)

1%

40%

5.5.6

F038

Under Current Trip Delay

1 - 60 seconds

1 second

2 seconds

5.5.6

F039

Coast Down Lockout Timer

0=Disabled
1=Enabled

1

0 (Disabled)

5.5.6

F040

Coast Down Lockout Time

1 - 60 minutes

1 minute

5 minutes

5.5.6

F041

Starts per Hour Lockout

0=Disabled
1=Enabled

1

0 (Disabled)

5.5.6

F042

Maximum Starts per Hour

1 - 10

1

2

5.5.6

F043

Time Between Starts Lockout

0=Disabled
1=Enabled

1

0 (Disabled)

5.5.6

F044

Minimum Time Between Starts

1 - 60 minutes

1 minute

15 minutes

5.5.6

F045

Coast Down Timer Value

1 - 3600 Seconds

View Only

0

5.5.6

F046

Starts per Hour Timer Value

1 - 3600 Seconds

View Only

0

5.5.6

F047

Starts per Hour Count Value

1 - 10 Starts

View Only

0

5.5.6

F048

Time Value Between Starts

1 - 3600 Seconds

View Only

0

5.5.6

F049

Thermal Capacity to Start

0 - 100 % Thermal Capacity

View Only

0

5.5.6

P

rot

ec

tion Featu

res

Fn

Group

Function

Adjustment

Range

Setting

Increments

Factory

Setting

Section

F022

Kick Start

0=Disabled
1=Enabled

1

0 (Disabled)

5.5.4

F023

Kick Voltage

10 - 100%

1%

65%

5.5.4

F024

Kick Time

0.1 - 2 Seconds

0.1 second

0.8 seconds

5.5.4

Kic

k Sta

rt

Mode

Advertising