Universal Security Instruments MICN109L User Manual

Page 9

Advertising
background image

Page 9

The yellow wire is used only for multiple station operations with USI ELECTRIC or UNIVERSAL
Model alarms only. Connecting this yellow wire to any other circuits may result in damage
and alarm malfunction. When alarms are interconnected, all alarms must be powered from a
single AC branch circuit. If local codes do not permit, be sure the neutral wire is common to
both phases. The maximum wire run distance between the first and last alarm/device in an
interconnected system is 1,000 feet. NOTE: Use standard household wire (18 gauge or larger,
rated at least 300V, as required by local codes) available at all electrical supply/hardware
stores.

The wiring to be used shall be in accordance with the provisions of Articles 210 and 300.3(B)
of the National Electrical Code, ANSI/NFPA 70. In addition, the resistance of the interconnecting
wiring shall be a maximum of 10 Ohms.

2.

Attach the mounting bracket to the electrical junction box.

3.

To activate 9 volt battery and alarm, hold the QUICK DRAW

(R)

battery drawer closed, pull and

remove the PULL-TAB. Confirm that the entire PULL-TAB has been completely removed. Discard
PULL-TAB.

4.

Plug the AC QUICK CONNECTOR into the alarm base. Push and twist the alarm clockwise
onto the mounting bracket.

5.

See "OPTIONAL TAMPER RESISTANT FEATURES" and "TO ACTIVATE THE LOCKING
FEATURES" instructions on Page 7.

6.

Turn on AC power and check the LED's for proper operation. The green LED should be on to
indicate AC power. The red LED blinks on once approx. every 40 seconds to indicate proper
operation.

IMPORTANT!

The battery backup is designed to provide short-term emergency power to the CO and Gas Alarm.
Actual backup time depends on the strength (freshness) of the battery. The battery backup will not
work unless a good battery is properly installed.

When the alarm utilizes battery backup power, the natural gas sensor will operate the alarm and will
sample less frequently to extend battery life. Natural gas could be present during this period between
samples without the alarm sounding, especially if there is a rapid buildup of natural gas.

OPERATION, TESTING & MAINTENANCE

OPERATION: The alarm is operating once the AC power is connected and turned on (the battery
must also be installed). When products of combustion are sensed, the alarm sounds a loud alarm
which continues until the air is cleared.

LOW BATTERY ALARM: If the alarm chirps once approx. every 40 seconds, please verify that the
battery activation pull tab has been completely removed, the battery polarity is correct and the
battery terminals are making contact with the alarm contacts in the battery compartment. If the
battery continues to chirp, replace the 9 volt battery.

This alarm incorporates the NFPA recognized horn signal for evacuation. During alarm mode, the
horn produces three beeps followed by a two second pause and then continually repeats.

READY/ACTIVE CONDITION: The red LED blinks on once approx. every 40-45 seconds to indicate
the alarm is properly functioning.

LOCAL ORIGINATING SMOKE ALARM CONDITION: The red LED blinks on approx. every 2
seconds and the alarm emits a loud, pulsating alarm sound.

NON-ORIGINATING SMOKEALARM CONDITION: The red LED is off and the alarm emits a loud,
pulsating alarm.

GREEN LED: The green LED is on whenever AC power is turned on.

CO ALARM: The alarm signal is 4 beeps, 2 second pause, repeat. The green LED turns off when
the 4 beeps start. The red LED blinks in sync with the cycle of 4 beeps.

GAS ALARM: The alarm signal is 1 beep, 1 second pause, repeat. The green LED blinks off. The
blue LED blinks in sync with the horn beep every second.

NUISANCE ALARM: If the horn signals for no apparent reason and no obvious hazard is present,
please verify that the alarm is mounted in the correct location. Reset the alarm as instructed in the
Operational Summary.

Advertising
This manual is related to the following products: