CLEARANCES TO COMBUSTIBLES

The stove must be installed with the following minimum clearances to side and back wall combustible materials. NOTE:

These are minimum clearances to combustible walls established by the testing lab. The amount of room needed on the left

side of the unit to access the electrical panel is (6) six inches (152mm).

PARALLEL - A - Left Sidewall to Top Edge of Unit

6 in./152mm

B - Sidewall to Flue

5 in./127mm

C - Backwall to Flue

3 in./75mm

D - Backwall to Unit

9 in./228mm

E - Right Sidewall to Top Edge of Unit

2 in./50mm

CORNER - F - Adjacent Wall to Flue

3 in./75mm

G - Adjacent Wall to Unit

4 in./100mm

BACK WALL

SIDE WALL

SIDE WALL

Backwall / Sidewall

Parallel

BACK WALL

Corner Installation

NOTE:

Allow sufficient space to remove the left and right side panels for maintenance purposes.

6”

min.

HEARTH PROTECTION

These clearances must be maintained and may only be reduced by means approved by the regulatory authority

6”

min.