The heater regulator controls the burner pressure which should be checked at the pressure test
point located on the front of the main control and is accessible by removing the control panel
on the right side of the heater.

The pressure should be checked with the heater burning and the control set to high (HI).

The pressure regulator is preset and locked to avoid tampering. If the pressure is not as
specified in Product Specifications (Page 5), contact your dealer and replace the regulator.

The appliance and its individual shutoff valve must disconnected from the gas supply piping
system during any pressure testing of that system at test pressures in excess of ½ psi (35 kPa).

GAS CONNECTION,

CONTINUED...

GAS PRESSURE CHECK

The gas inlet connection is 3/8" NPT, made at the top of the
control cover inside the access door of the mantel. Run gas
line from the gas supply to the connection. A flex pipe
connector is suggested for easy connection.

Test all gas joints from the gas meter to the heater for leaks
using soap and water solution after completing connection.
DO NOT USE AN OPEN FLAME.

FIGURE 6. Flex Pipe Connected to control

GAS INLET