Rules for Connector
Pipe Installation

1. The crimped end of the chimney connector fits

inside the furnace flue collar. Install additional chim-

ney connectors and elbow with the CRIMPED END

TOWARD THE FURNACE. This will allow any

condensation in the flue to run back into the furnace.

Use 6" dia. steel pipe and elbows for connection to

chimney. Never use less than 24 gauge and al-

though blued steel is satisfactory, high temp painted

black is much more desirable.

2. Slope any horizontal pipe upward toward the

chimney at least 1/4 inch for each foot of horizontal

run.

3. You must have at least 18 inches of clearance

between any horizontal piping and the ceiling.

(See Fig. 3)

4. The chimney connector must not extend into the

chimney flue. (See Fig. 6)

5. Seal each chimney connector pipe joint with fur-

nace cement. Also seal the pipe at the chimney.

6. Use 3 sheet metal screws at each chimney pipe

joint to make the piping rigid.

7. The chimney connector may include a section for

a barometric draft regulator between the furnace and

the chimney (Fig. 4,5, &7). The barometric draft

regulator must be installed in the same room (same

pressure zone) as the furnace.

8. Install the barometric draft regulator strictly in

accordance with the instructions that are provided

with the barometric draft regulator.

9. A solid damper must be used in the chimney

connecting pipes between the flue collar and the

chimney. When used in conjunction with a baromet-

ric draft regulator, the solid damper must be placed

between the barometric and the chimney. (See Fig.

4,5,7)

Adjusting the Barometric Draft Regula-

tor

1. Drill a hole in the chimney connector within 18" of

the flue collar below the barometric draft regulator

just large enough for the tube of the manometer.

2. Build a fire after all chimney connections have

been made.

3. Use a manometer to measure the draft in the flue.
4. Adjust the Barometric Draft Regulator to obtain a
draft of 0.05 - 0.06" W.C. under stable fire conditions.

RIGHT

WRONG

WRONG

Fig. 6

6" SOLID DAMPER

6" BAROMETRIC
DRAFT REGULATOR
(OPTIONAL)

MEASURE FLUE
DRAFT HERE

NON-COMBUSTIBLE
INSTALLATION PER
NFPA 211

Fig. 7