Appendix g, Make-up heat requirements, 1200 cfm unit – Venmar 700 cfm User Manual

Page 20

Advertising
background image

Page 20

Although the 600 cfm, 700 cfm and 1200 cfm models have good ef

ficiencies, the supply air could be colder than the ambient room

air

. It is possible to eliminate the

discomfort associated with this temperature dif

ference by installing an electric duct heater

.

This will temper the air before i

t is distributed throughout the building.

The table below gives the heating requirements at dif

ferent temperatures and airflows.

OUTDOOR

AIR -40°F

(- 40°C)

OUTDOOR

AIR -22°F

(-30°C)

OUTDOOR

AIR -4°F

(-20°C)

OUTDOOR

AIR +14°F

(-10°C)

OUTDOOR

AIR +32°F

(0°C)

Desired Air

T

emperature

Desired Air

T

emperature

Desired Air

T

emperature

Desired Air

T

emperature

Desired Air

T

emperature

55°F(13°C)

68°F(20°C)

73°F(23°C)

55°F(13°C)

68°F(20°C)

73

°F(

23°C

)

55°F(13°C)

68°F(20°C)

73°F(23°C)

55°F(13°C)

68°F(20°C)

73°F(23°C)

55°F(13°C)

68°F(20°C)

73°F(23°C)

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

1250

590

14.6

19.9

21.9

1

1.2

16.5

18.5

7.8

13.1

15.2

4.4

9.7

1

1.8

1.0

6.3

8.4

1200

566

13.5

18.6

20.6

10.4

15.5

17.4

7.2

12.3

14.3

4.0

9.1

1

1.1

0.8

5.9

7.9

1

150

542

12.6

17.4

19.3

9.6

14.5

16.4

6.6

1

1.5

13.4

3.6

8.5

10.4

0.7

5.5

7.4

1

100

519

1

1.2

15.9

17.7

8.5

13.2

15.0

5.8

10.5

12.3

3.1

7.7

9.6

0.4

5.0

6.8

1050

495

10.7

15.2

16.9

8.1

12.6

14.3

5.5

10.0

1

1.7

2.9

7.4

9.1

0.4

4.8

6.5

1000

472

9.9

14.1

15.7

7.4

1

1.7

13.3

5.0

9.3

10.9

2.6

6.9

8.5

0.2

4.4

6.1

900

425

8.5

12.4

13.8

6.4

10.2

1

1.7

4.3

8.1

9.6

2.2

6.0

7.5

0.1

3.9

5.4

800

377

7.0

10.4

1

1.7

5.2

8.6

9.9

3.4

6.8

8.2

1.7

5.0

6.4

-

3.3

4.6

700

330

5.1

8.1

9.3

3.7

6.7

7.9

2.3

5.3

6.5

0.9

3.9

5.1

-

2.5

3.7

1200

CFM UNIT

Supply Air

Supply Air

(cfm)

(L/s)

OUTDOOR

AIR -40°F

(- 40°C)

OUTDOOR

AIR -22°F

(-30°C)

OUTDOOR

AIR -4°F

(-20°C)

OUTDOOR

AIR +14°F

(-10°C)

OUTDOOR

AIR +32°F

(0°C)

Desired

Air T

emperature

Desired

Air T

emperature

Desired

Air T

emperature

Desired

Air T

emperature

Desired

Air T

emperature

55°F(13°C)

68°F(20°C)

73°F(23°C)

55°F(13°C)

68°F(20°C)

73

°F(

23°C

)

55°F(13°C)

68°F(20°C)

73°F(23°C)

55°F(13°C)

68°F(20°C)

73°F(23°C)

55°F(13°C)

68°F(20°C)

73°F(23°C)

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

kW

700

330

7.4

10.4

1

1.5

5.6

8.6

9.7

3.9

6.8

8.0

2.1

5.1

6.2

0.3

3.3

4.4

650

307

6.6

9.4

10.5

5.0

7.8

8.9

3.4

6.2

7.3

1.8

4.6

5.6

0.2

3.0

4.0

600

283

5.9

8.5

9.4

4.5

7.0

8.0

3.0

5.6

6.5

1.6

4.1

5.1

0.1

2.7

3.7

550

259

5.2

7.6

8.5

3.9

6.3

7.2

2.6

5.0

5.9

1.3

3.7

4.6

0.1

2.4

3.3

500

236

4.0

6.1

7.0

3.0

5.1

5.9

1.9

4.0

4.9

0.9

3.0

3.8

-

1.9

2.7

450

212

3.0

4.9

5.6

2.1

4.0

4.8

1.3

3.2

3.9

0.4

2.3

3.1

-

1.5

2.2

400

189

2.2

3.9

4.6

1.5

3.2

3.9

0.9

2.5

3.2

0.2

1.9

2.5

-

1.2

1.8

600 and 700

CFM UNIT

Supply Air

Supply Air

(cfm)

(L/s)

NOTE:

The data does not reflect a reduction in ef

fectiveness due to frosting. Based on the

standard air at: 1.2 Kg/m

3

and Cp = 1.0 KJ/Kg°C

13.35 lb/ft

3

and Cp = .24 Btu/lbm°F

Appendix G

Make-up Heat Requirements