Dayton diesel electric generator, 4w315c, Operation – VDO Dayton 4W315C User Manual

Page 12: Dayton operating instructions and parts manual 12

Advertising
background image

Dayton Operating Instructions and Parts Manual

12

Dayton Diesel Electric Generator

®

4W315C

107358

W

(Neutral)

X

(Hot)

Ground
(Green)

120 Volt

30 Amp

G

W

X

L5-30P
Plug

Operation

HIGH AND LOW TEMPERATURE
OPERATION

Air temperature affects generator output.
Output drops 1% for each 10

° tempera-

ture rise above 60

° F. Very low tempera-

tures may make the engine hard to start.
See engine owner’s manual for more
information.

GENERAL INFORMATION

This generator is not large enough to
power your entire home. Do not connect
generator to any existing electrical circuits.
Plug items directly into generator recep-
tacles. Do not exceed amperage rating of
receptacles. Only use grounded cords.

Use only in well-
vented areas. Make

sure area has plenty of free-moving,
fresh, outside air. Never run generator
in an enclosed or confined area. Never
run generator inside occupied building.
engine exhaust contains poisonous
carbon monoxide gas. Overexposure
will cause loss of consciousness and
will lead to death.

Never connect
generator to any

existing electrical circuits. The genera-
tor output will back-feed into the
utility power line. This may electrocute
a power company line repair person.
Also, if generator is powering electri-
cal circuits, the chance of an electrical
fire exists.

NOTE: We supply the engine owner’s
manual with generator. Refer to that
manual for questions concerning engine
operation.

USING RECEPTACLE

NOTE: Do not exceed amperage rating of
receptacles. Exceeding rating will trip
receptacle circuit breaker.

Use receptacles properly. Improper use
could damage generator. Use only
grounded extension cords. Power only
grounded or double-insulated items. Do
not overload receptacles. These genera-
tors have the following receptacles (See
Figure 16):

• 120V, 15-amp duplex receptacle

• 120V, 15-amp GFCI duplex receptacle

• 120V, 30-amp twist-lock receptacle

• 120/240V, 20-amp twist-lock recep-

tacle

RE

SE

T

TE

ST

120

V

OL

TS

RES

ET

RES

ET

EN

M

0000

000

5

HOURS 1/10

120

ONLY

120

240V

120V, 30-Amp
Twist-Lock

120V, 15-Amp Duplex

120/240V, 20-Amp
Twist-Lock

Figure 16 – Receptacle Locations

POWER CORD AND PLUG REQUIRE-
MENTS

120V, 30-amp twist-lock receptacle

• NEMA L5-30P plug

• Three-wire, 30-amp cord

120/240V, 20-amp twist-lock receptacle

• NEMA L14-20P (20-amp) plug

• Four-wire, 20-amp cord

w

G

Y

X

Ground

X

(Hot)

W

(Neutral)

Y

(Hot)

Ground

(Green)

L14-20P
Plug

120V

120V

Neutral

120/240 Volt

20 Amp

Figure 17 – Cord and Plug Configurations

PRESTART

Operate generator on a firm, dry, and
clean surface. The surface must be level.
Protect generator from heavy dust, sand,
dirt, rain, or snow. Do not locate genera-
tor near standing water or snow. Make
sure area is well-vented.

Only responsible
adults should use

generator. Never let anyone operate
generator without proper instructions.

NOTE: If oil level is too low, oil alert
system will keep engine from starting (See
“Oil Alert System,” page 5). Make sure oil
level is full before starting. See Engine Oil,
page 8.

Before starting the engine, disconnect all
electric loads from generator.

You may need to bleed fuel line to remove
trapped air

• if starting engine for first time

• if starting engine after allowing

generator to run out of fuel

120V, 15-Amp GFCIDuplex