CAUTION: Never connect heater directly to the propane/LP supply.

This heater requires an external regulator (not supplied). Install the
external regulator between the heater and propane/LP supply.

The installer must supply an external regulator. The external regulator will reduce incoming
gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water.
If you do not reduce incoming gas pressure, heater regulator damage could occur. Install
external regulator with the vent pointing down. Pointing the vent down protects it from
freezing rain or sleet.

Providing Gas Piping to Furnace

You must provide gas piping from gas source to furnace. The gas piping must be in a vertical
position where it connects to the furnace. This prevents interference with front cover
installation.

Consult your local gas company for proper routing of the gas lines.

Pipe size is determined by the length of pipe from the gas source to the furnace and the total
BTU load on the gas source.

Add the total BTUs required for all appliances connected to the gas source including this furnace.
Divide this number by 2500. This will give you the approximate cubic feet per hour needed.

Example:

40,000 BTU/Hr

+ 15,000 BTU/Hr for other gas appliances

55,000 BTU/Hr total

55,000

÷

2500 = 22

Locate 22 or higher on chart below.

According to the chart below, you should use 40 feet or less of 3/8" pipe, 125 feet
or less of 1/2" pipe, etc...

MINIMUM

IRON PIPE

SIZE

LENGTH OF PIPE (FEET)

10

20

30

40

50

60

70

80

90

100

125

150

175

200

3/8"

47

32

26

22

19

18

16

15

14

13

12

11

10

1/2"

87

61

48

42

37

33

30

28

26

25

22

20

18

17

3/4"

184

126

100

86

76

69

63

59

55

52

48

42

39

36

1"

344

232

189

162

142

129

119

112

106

99

86

79

73

66

1

1

/

4

"

696

484

391

331

291

265

245

232

212

202

182

166

149

139

1

1

/

2

"

1060

729

590

504

444

404

371

351

324

305

272

252

232

212

2"

2022

1392 1094

961

842

762

696

656

616

576

517

470

430

404

2

1

/

2

"

3182

2188 1790 1524 1326 1226 1127 1060

994

928

829

749

969

649

3"

5635

3911 3116 2718 2387 2154 1989 1856 1724 1657 1458 1326 1226 1127

4" 11602

7956 6431 5503 4906 4508 4110 3845 3580 3381 2983 2718 2519 2320

IMPORTANT:

Check gas line pressure at gas meter before connecting furnace to gas line. Gas

line pressure must be no less than 11 inches of water and no greater than 13 inches of water.
Gas pressures and input to the burners must not exceed the rated input and pressure shown on
the rating plate. For propane/LP gas, manifold pressure should be 10 inches of water. For
elevations above 2000 feet, reduce rating 4% for each 1000 feet above sea level (U.S.A. only).

INSTALLATION