Press the SYSTEM button until OFF is displayed, then press the

and

simultaneously

INSTALLER/CONFIGURATION MENU

Press

Displayed

Press

or

Step

Button(s)

(Factory Default)

to select

Comments

1

System

MS 2

SS1, HP2, HP1

Selects Single stage, Multi-stage, or Heat Pump

(Single stage or 2-stage) System Configuration

2

System

7d

5d, 0d

Selects Programs Per Week

3

System

PRG 4

PRG 2

Selects Programmable Periods (PRG 2 = 2

programmable periods; PRG 4 = 4 programmable periods)

4

System

4:00 HOLD

0:15 to 4:00

Selects Temporary Program Override Time

(increments of 15 minutes)

5

System

EMR

OFF

Selects Energy Management Recovery OFF or ON

(ON)

6

System

FA

SL

Selects Fast or Slow Cycle Selection

7

System

CL

CL

Selects Compressor Lockout CL OFF or ON

(OFF)

(ON)

8

System

CDL

CDL

Selects Backlight Display

(ON)

(OFF)

9

System

FA

FA

Selects Fast Second Stage ON or OFF

(ON)

(OFF)

10

System

0 FLTR

50-1950 (increments of 50)

Selects filter replacement run time

11

System

0°F

4 LO to 4 HI

Selects Temperature Display Adjustment 4 LO to 4 HI

(Room Temperature)

12

System

°F

°C

Selects temperature display or °C selection

13

System

AU On

OFF

Selects AUTO Mode ON or OFF

14

System

LR

LR 62 to LR89

Selects Limited HEAT range

(90)

15

System

LR

LR 46 to LR 82

Selects Limited COOL range

(45)

16

System

CA

CA

Feature Not Available

(OFF)

(ON)

17

System

(ON)

Selects Keypad Lockout

(OFF)

18

System

0

001 to 999

Selects Keypad lockout combination number

Press System to set code

19

Run

Returns to the OFF position

CONFIGURATION MENU

CONFIGURATION MENU

CONFIGURATION MENU

CONFIGURATION MENU

CONFIGURATION MENU

programmable, SYSTEM button selection will skip

Programmable periods (item 3), programmable hold time
(item 4) and EMR (item 5).

3) Programmable Periods – This control can be configured

for 4 or 2 programmable periods. The display indicates
“PRG 4” in the display as default. The programmable
periods can be toggled to “PRG 2” by pressing the
or

keys.

4) Select Temporary Program Override Time – The thermo-

stat can hold any temperature you set it to for the amount
of time you select on this option. Your choices are 0:15 to
4:00 hours in 15 minute increments.

Example:

a. You have selected 3:00 hours for the Temporary Pro-

gram Override time period.

b. With the thermostat set to Heat or Cool, press

or

to set the temperature to your preference.
The thermostat will maintain this temperature setting
for 3 hours with “HOLD” blinking to remind you it is
in Temporary Hold. After 3 hours, the thermostat will
go back to the program temperature and “HOLD” will
no longer blink or display.

Advertising