19. The gateway instance represents the EZ-ZONE

®

control, in this case, PM 1-4. The enable

gateway instance simply turns on that particular gateway where there is a direct correlation

between gateway instance 1 and EZ-ZONE

®

PM controller 1. Likewise, that relationship

continues through gateway instance 16 and EZ-ZONE

®

PM

controller 16. The gateway

instance will always equate to the Standard Bus controller with the same address 1-16.

The CIP offset allows for the PLC or any master on the DeviceNet

TM

side to read or write the

same member from any of the four controllers on the Standard Bus network via an explicit

message.

Configuring the DeviceNet

TM

Scanner (1769-SDN) Using RSLogix 5000


20. In the examples that follow please note that the PLC being used is a CompactLogix L32E. If

using other PLCs the steps will vary slightly but the overall concepts will be the same. As you
might guess some configuration is required on the PLC side prior to getting started with the
programming.

21. Insert a DeviceNet

TM

scanner into the I/O structure of the PLC. Notice below the input and

output size correlates directly to what was configured in RSNetWorx (step 15).