9 subassembly identification – Watlow Electric Revision 5 User Manual

Page 14

Advertising
background image

9

2.9 SUBASSEMBLY IDENTIFICATION

A32-PIOM: PROCESSOR I/O MODULE includes factory selectable
communication interface [RS-232 or current loop], 32 control outputs, 24 digital
outputs, and 16 digital inputs.

A32-RRAIM: REED RELAY ANALOG INPUT MODULE for 16 mixed sensor
inputs including direct connection of thermocouples [J, K, or T] or millivolt [ -5 to
60mv]. Includes reference junction sensors for thermocouple inputs.

A32-SSAIM: SOLID STATE ANALOG INPUT MODULE for 32 mixed analog
inputs including direct connection of thermocouple or millivolt inputs. Includes
reference junction sensors for thermocouple inputs.

A32-IAIM-SIXX: SPECIAL INPUT SCALING for RRAIM or SSAIM to connect
milliamp, voltage, or RTD inputs. Consult ANAFAZE for details.

A32-AOM : ANALOG OUTPUT MODULE with 16 analog outputs set for both 0
to 5Vdc and 4 to 20ma. Consult ANAFAZE for other output levels.

A32-H6: 6 SLOT HOUSING including passive interconnection backplane and up
to three blank front panels. Can be mounted on a panel or in a standard 19 rack
[12.5" high, 19"wide, 7.5"deep].

A32-H3: 3 SLOT HOUSING including passive backplane and up to one blank
front panel. For panel mounting 12.5" high, 10.7" wide and 7.5" deep.

A32-PS: POWER SUPPLY: mounted on a blank front panel with wiring to
passive backplane. Supply can be externally mounted or plugged into a module
slot. Dimensions: 9" high, 2" wide and 5" deep.

A32-OS: OPERATOR STATION: allows for data display and setpoint entry away
from the system computer [requires ANASOFT].

ANASOFT-32: Software operating system for IBM PC and compatible computers.

CABLES: Interconnection cables with an RS-232 connector on one end and wires
at other for connection to SYSTEM 32 terminals:

CA-232M

25' RS-232 cable male computer connector

CA-232F

25' RS-232 cable female computer connector

Advertising