Troubleshooting, Continued, Chart 1 – Weil-McLain PFG-7 User Manual

Page 14

Advertising
background image

14

Part Number 550-110-031/0605

EGH-85 & 95 Series 4 and PFG-6 & 7 Series 6 & 7

Is 24VAC present across transformer terminals C & Y?

Is damper harness securely plugged in at both ends?

Secure connections.

Check for open thermostat, LWCO, high limit, spill switch or
rollout thermal fuse element contacts or check for loose
wire connections.

If LWCO, spill switch or rollout thermal fuse
element contacts are open, determine cause
and correct condition. Failure to do so will
cause severe personal injury, death or
substantial property damage.

Check/repair out of round stack section. Does vent damper
rotate open?

Is 24VAC present across transformer terminal C and yellow
wire on vent damper connector?

Is 24VAC present across gas valve terminals?

Open thermostat contacts for 30 seconds. Vent damper will
rotate to closed position. Close thermostat contacts. Vent
damper will rotate to open position. Is 24VAC present
across gas valve terminals?

Remove damper harness from
damper harness plug.
TEMPORARILY install jumper
between terminal 2 and
terminal 5 on damper plug in
boiler wiring harness. See
figure, right. Does boiler fire?

No

Yes

No

Yes

Chart 1:

Boiler will not fire — water boilers without tankless

Check for loose wire connections or bad relay on
transformer.

No

Yes

Is vent damper rotated open?

No

Yes

No

Yes

Replace actuator.
Retest.

Check continuity of each wire in damper harness. Does
continuity exist for each wire? See Table below.

Replace damper
wiring harness.
Retest.

Replace gas valve.
Retest.

Is main flame on now?

No

Yes

Retest

No

Yes

No

Yes

No

Yes

No

Yes

Replace damper
actuator. Retest.

Turn gas valve cock to
ON position. Retest.

Replace gas valve.
Retest

Is gas valve cock turned to ON position?

No

Yes

Troubleshooting

continued