12. DUCTS AND REGISTER MEASUREMENTS

(sample calculations)

SIMPLIFIED METHOD

DISTRIBUTION SYSTEM

Ducts size (heat)

4 inch outlet reduce by 1”

5 inch outlet reduce by 2” Always by 8” thick

6 inch outlet reduce by 3”

N.B.: The main duct must be reduced every 2

outlets.

Ducts specifications (heat)

Dimensions Length Elbow Average equivalence

4”

10’

1 x 90

o

Max 4,000 Btu

5”

10’

1 x 90

o

Max 6,000 Btu

6”

10’

1 x 90

o

Max 7,000 Btu

DAMPER

For a 4” warm air outlet: 2” x 10” damper

For a 5” warm air outlet: 2” x 12” damper or 4” x 10”

For a 6” warm air outlet: 2” x 14” damper or 4” x 12”

WARM AIR SYSTEM INSTALLATION

HOUSE DIMENSIONS
Example: 28 x 40 bungalow: 1,120 sq. ft.

28 x 40 x 8: 8,960 cu. ft. x 1.8 Ch. air/hr:

16,128 Btu


Exposed walls:


40 + 40 + 28 + 28: 136 x 8: 1,088 cu. ft. x 22: 23,936 Btu

Number of windows:


12 of 3 x 4: 144 x 60:

8,640 Btu


Number of doors:


2 x 3 x 7: 42 x 100:

4,200 Btu

52,904 Btu


Non-insulated basement:

25%

Insulated basement:

15%

7,906 Btu

or 54 Btu per sq. ft.

60,840 Btu

FOR ELECTRIC ELEMENTS 80%:48,672 Btu or 14,28 kW

TO BE ADDED: House 1 1/2 floor = 25%

House 2 floors = 40%



BEDROOM (for example: 12 x 12)

12 x 12 x 8: 1,152 cu. ft. x 1.8 Ch. air/hr:

2,074 Btu

Exposed walls:

12 + 12 x 8: 192 x 22:

4,224 Btu

Windows:

3 x 4 x 60

720 Btu

7,018 Btu