Operation — sequence, Gold cgs gas-fired water boiler — boiler manual – Weil-McLain GOLD CGS 550-110-260/0107 User Manual

Page 31

Advertising
background image

Part number 550-110-260/0107

31

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Operation — sequence

9a

Figure 18 Control module sequence of operation — status light indications

1.

Read appropriate Operating instructions

in

Section

9c

. This information is also located on a

label on the inside of the boiler jacket door panel.

.

Raise

room thermostat to call for heat.

3.

Circulator energizes.

If limit circuit is closed, the

inducer starts. After pressure switch proves proper

airflow, control module initiates a 30-second pre-

purge.

4.

Control module sparks

the pilot and opens pilot

valve in main gas valve.
a. If pilot

does not

light within 15 seconds, pilot

valve is closed and spark generator is turned

off. Control module initiates a 15-second

postpurge, then starts a new cycle.

b. If pilot

does

light and control module senses

flame current, spark generator is turned off

and main valve opens.

5. During

main burner operation

:

a. Control module monitors pilot flame current.

If signal is lost

, main valve closes, spark gen-

erator activates and sequence returns to step

4

.

b.

If power is interrupted

, control system

shuts

off

pilot and main gas valves and restarts at

step

1

when power is restored.

6. In the event the

limit control shuts down the

boiler

— The control module closes the pilot and

main gas valves, but keeps the inducer operating for

15-second postpurge.
— The circulator continues to operate.

.

Lower

room thermostat setting to stop call for

heat. Thermostat is satisfied — Pilot and main gas

valves are closed — Inducer operates for 15-second

postpurge — Circulator is shut off.

8. Boiler is now in the

off cycle

.

9.

Repeat

steps

1

through

6

several times to verify

operation.

10.

Return

the thermostat to normal setting.

11. Set thermostat heat anticipator setting to 0.4 amps,

adjusted for gas valve and control current.

Advertising