Field wiring – Weil-McLain Ultra Electric Water Heater User Manual

Page 9

Advertising
background image

Part number IWHA016A/1103

9

PLUS Line Instruction Manual Supplement

PLUS &

PLUS

WATER

HEATERS

WITH

GAS

-

FIRED

WATER

BOILERS

Wiring a system circulator

1. For combined systems, to activate a system

circulator when the Boiler circulator operates, wire
as shown at bottom of Figure 7, page 8.

2. You must install a relay as shown. DO NOT wire in

parallel with the Boiler circulator. See CAUTION
in Figure 7.

Routing line voltage wiring

1. Route line voltage connections to the jacket

openings shown in Figure 8.

Low voltage connections (Fig. 9)

1. Connect low voltage wiring to low voltage terminal

strip (Figure 9, item 1) as shown in Figure 9 and
the boiler wiring diagram.

2. Route all low voltage wires through grommeted

jacket opening to right of low voltage terminal strip,
as shown in Figure 8.

Room thermostat (space heating)

1. For combined space heating/water heating systems,

connect Figure 9, item 2, room thermostat or end
switch (isolated contact only) between terminals 5
and 6.

2. Install thermostat on inside wall away from

influences of drafts, hot or cold water pipes, lighting
fixtures, television, sunrays, or fireplaces.

3. Thermostat anticipator (if applicable):

a. If connected directly to boiler, set for 0.1 amps.
b. If connected to relays or other devices, set to match

total electrical power requirements of connected
devices. See device manufacturers’ specifications and
thermostat instructions for details.

Outdoor temperature sensor

1. Outdoor reset operation applies only to combined

space heating/water heating systems.

2. Connect outdoor temperature sensor (Figure 9,

item 6) between terminals 1 and 2 to enable
outdoor reset operation of the Ultra boiler. If fixed-
temperature operation is required, do not install
outdoor sensor.

3. Mount sensor on exterior wall, shielded from direct

sunlight or flow of heat or cooling from other
sources.

4. Install a summer/winter switch (Figure 9, item 7)

across terminals 1 and 2 to force fixed-temperature
operation during summer months. (When the

switch is closed, boiler will attempt to maintain
constant temperature.)

5. Route sensor wires through the grommeted hole

at right of the electrical entrance (see Figure 8).

PLUS water heater thermostat

1. Connect PLUS water heater aquastat terminals “C”

and “1” to Ultra Boiler low voltage terminal strip
between terminals 3 and 4 (Figure 9, item 3).

Additional limits

1. Connect additional limit controls and interlocks

between the terminals shown in Figure 9.

2. Controls connected between terminals 6 and 7 (see

Figure 9, item 4) will cause a soft lockout
(automatic reset). When limit(s) closes, boiler will
resume normal operation.

3. Controls connected between terminals 6 and 8 (see

Figure 9, item 5.) will cause a hard lockout (manual
reset). The boiler will only restart after the Ultra
display panel RESET switch is pressed.

Field wiring

(continued)

3

Figure 8

Routing field wiring

Advertising