Burner specifications and settings – Weil-McLain 702CRD-W User Manual

Page 2

Advertising
background image

Weil-McLain 88 Water and Steam Boilers — Series 2 —

For Light Oil-Fired Burners

2

Part No. 550-142-030/0508

Burner data

Table 1

Boiler

Model

Number

Burner Input

(Forced Draft)

No. 2 Oil

Gph

Low Fire

Firing Rate

No. 2 Oil

Gph

Positive

Pressure In

Firebox

Inches W.C.

Standard

Burner

Model

Designation

Standard

Combustion

Control

Starting

Head

Setting

Approximate

Air Settings

Low Fire

488R

6.90

3.90

0.55

702CRD-W

60200

7/32

5/16

488

7.00

4.00

0.55

702CRD-W

60200

7/32

5/16

588

9.40

5.42

0.61

702CRD-W

60200

13/16

1/2

688

11.80

6.60

0.55

801CRD-W

60200

3/16

1/4

788

14.20

7.00

0.60

801CRD-W

60200

5/8

1/2

888

16.60

8.00

0.85

801CRD-W

60200

1

3/8

988R

17.20

8.90

0.65

1050FFD-W

60200

3/8

3/8

988

18.80

8.92

0.70

1050FFD-W

60200

1/2

1/4

1088R

20.00

9.60

0.70

1050FFD-W

60200

1/2

3/4

1088

21.50

10.10

0.70

1050FFD-W

RM7840L-1018

1/2

3/4

1188

23.50

12.00

0.75

1150FFD-W

RM7840L-1018

1/4

11/16

1288

26.00

12.54

0.75

1150FFD-W

RM7840L-1018

7/16

7/8

1388

28.50

13.44

0.80

1150FFD-W

RM7840L-1018

11/16

7/8

1488

31.00

15.10

0.75

1150FFD-W

RM7840L-1018

1

1

Burner capacities listed for elevations up to 2,000 feet. For

1.

higher elevations, consult local Weil-McLain distributor/

agent or sales office.

Light oil ratings based on No. 2 fuel oil with heating value of

2.

140,000 Btu per gallon.

Boiler-burner unit to be adjusted to achieve +0.10 inches

3.

W.C. pressure at the flue collar, resulting in positive pressure

in firebox as listed.

Combustion Controls:

4.

60200 combustion safety control uses a cadmium sulfide

a.

cell flame detector to monitor oil flame; provides inter-

rupted duty, recycle type operation, latch-up feature,

30-second oil valve delay on, 30-second post purge, alarm

contacts and safety monitor circuit.

RM7840L-1018 combustion safety control (for over 20

b.

GPH applications) uses an ultraviolet flame detector to

monitor oil flame and provides purge timings.

All motors furnished with integral overload protection with

5.

manual reset.

Mechanical pressure atomizing oil control system with on/

6.

off operation, low fire start, high fire run and two-position

air control is standard. Low-High-Low fire operation can

be obtained by addition of SPST temperature or pressure

controller.

120/60/1 control circuit is used for all burners.

7.

Notes for Table 1 and Table 2

Burner specifications and settings