2-2

IPS-800/IPS-1600 Series - User’s Guide

Bus "A" Switched Plugs and Plug Indicators: AC Outlets that can be

switched On, Off or rebooted in response to user commands.
IPS-800: Four 100-120 VAC, NEMA 5-15 Outlets with indicator

lights. 15 Amps Total Load.

IPS-1600: Eight 100-120 VAC, NEMA 5-15 Outlets with indicator

lights. 15 Amps Total Load.

IPS-800-CE: Four 208-240 VAC, IEC-320-C13 Outlets with indicator

lights. 10 Amps Total Load.

IPC-1600-CE: Eight 208-240 VAC, IEC-320-C13 Outlets with

indicator lights. 10 Amps Total Load.

Bus "B" Switched Plugs and Plug Indicators: AC Outlets that can be

switched On, Off or rebooted in response to user commands. Includes

same components listed in item 3 above.

Default Button: This button can be used to either reset the unit to default

parameters or manually toggle all plugs On or Off:
Default Parameters: With the Master I/O Switch (Master Power

Switch) set in the Off position, press and hold the Default Button, then

set the Master I/O Switch in the On position and release the Default

Button. All menu defined parameters will be reset to default values.

Manual Plug Toggle: Press the Default Button and hold it down for

three seconds. All IPS power outlets will be toggled On or Off.

Note:

If desired, the Default Button’s manual plug control

capabilities can also be disabled as described in Section 5.3.1.

Unit Status Indicators: Two LED Indicators which function as follows:

ON: Lights when power is applied to the IPS Unit.
RDY: Flashes continuously when the IPS is ready to recieve

commands.

Network Port and Activity Indicator: An RJ45 Ethernet Port

for connection to your TCP/IP network. The default IP Address is

192.168.168.168, for more information, please refer to Section 5.3.4. The

Activity Indicator flashes to indicate activity at the Network Port.

Master I/O Switch (Master Power Switch): Applies power to the IPS

Unit. This switch must be "On" in order for the IPS to function. Note

that this switch is not used to set the On/Off status of the switched outlets.

COM / RS232 Port: A DB9, RS232 serial port (DTE), for connection to

a local terminal or external modem, as described in Section 4.3.