GAS INSTRUCTIONS

INSTALL GAS SUPPLY

General Specifi cations for Piping
Note - Contact your local municipality for building codes regulating
outdoor gas barbecue installations. In absence of Local Codes, you
must confi rm to the latest edition of the
National Fuel Gas Code: ANSI Z
223.1/NFPA 54, or CAN/CGA-B149.1, Natural Gas and Propane Installation
Code. WE RECOMMEND THAT THIS INSTALLATION BE DONE BY A
PROFESSIONAL.
Some of the following are general requirements taken from the latest
edition of the National Fuel Gas Code: ANSI Z 223.1/NFPA 54, or CAN/
CGA-B149.1, Natural Gas and Propane Installation Code for complete
specifi cations.
This barbecue is designed to operate at 4.5 inches of water column

pressure (.16241 psi).

A manual shut-off valve must be installed outdoors, immediately ahead
of the quick disconnect.

An additional manual shut-off valve indoors should be installed in the

branch fuel line in an accessible location near the supply line

The quick disconnect connects to a 1/2 inch NPT thread from the gas

source. The quick disconnect fi tting is a hand-operated device that
automatically shuts OFF the fl ow of gas from the source when the
barbecue is disconnected

The quick disconnect fi tting can be installed horizontally, or pointing

downward. Installing the fi tting with the open end pointing upward can
result in collecting water and debris.

The dust covers (supplied plastic plugs) help keep the open ends of the

quick disconnect fi tting clean while disconnected.

Pipe compound should be used which is resistant to the action of natural

gas when connections are made.

The outdoor connector must be fi rmly attached to rigid, permanent

construction.

ƽ WARNING: Do not route the 10 foot hose under a

deck. The hose must be visible.

Gas Line Piping
If the length of the line required does not exceed 50 feet, use a 5/8" O.D.

tube. One size larger should be used for lengths greater than 50 feet.

Gas piping may be copper tubing, type K or L; polyethylene plastic tube,

with a minimum wall thickness of .062 inch; or standard weight (schedule
40) steel or wrought iron pipe.

Copper tubing must be tin-lined if the gas contains more than 0.3 grams

of hydrogen sulfi de per 100 cubic feet of gas.

Plastic tubing is suitable only for outdoor, underground use.
Gas piping in contact with earth, or any other material which may corrode

the piping, must be protected against corrosion in an approved manner.

Underground piping must have a minimum of 18" cover

Test Connections
All connections and joints must be thoroughly tested for leaks in accordance
with local codes and all listed procedures in the latest edition of the National
Fuel Gas Code: ANSI Z 223.1/NFPA 54, or CAN/CGA-B149.1

ƽ DANGER

Do not use an open fl ame to check for gas leaks. Be
sure there are no sparks or open fl ames in the area
while you check for gas leaks. This will result in a fi re
or explosion which can cause serious bodily injury or
death and damage to property.

LEAK CHECK PREPARATION

CHECK THAT ALL BURNER VALVES ARE OFF
Valves are shipped in the OFF position, but you should check to be sure that
they are turned OFF. Check by pushing down and turning clockwise. If they
do not turn, they are off. Proceed to the next step. If they do turn continue
turning them clockwise until they stop, then they are off. Proceed to the next
step.

Gas supply

Shut off

Locking shut off

Inside wall

Outside wall

Quick

disconnect

1/2

"

Pipe

nipple

Do Not Use

This is a typical installation
of a Weber

®

natural gas

barbecue. Local codes may
require different
installations.