Installer table – White Rodgers 90 SERIES User Manual

Page 5

Advertising
background image

5

* NOTE: COMP LOCK OFF permanently
defeats compressor lockout. You must turn
this selection ON if you do not have a
system that already provides compressor
short-cycle protection.
Please see “Lockout
Bypass Option” to temporarily override
compressor lockout.

INSTALLER TABLE

1

MLTI STG

HEAT PUMP

2

HEAT PUMP

(1)

2 or 3

Selects type of system. Selecting HEAT PUMP
makes additional menu items for heat pump
system available.

3

ELECT HEAT FAN

(ON)

OFF

Fan cycles with call for heat if ON. Fan always
cycles with pump stages.

4

SET CYCLE HEAT

(5 for multi-stage

13 for heat pump)

1 to 40 for multi-stage

9 to 40 for heat pump

5

SET CYCLE COOL

(13)

9 to 40

12

ECON

(OFF)

ON

15

REM SEN b

(OFF)

ON

16

REM SEN C

(OFF)

ON

Returns to normal operation

17

STAT SEN L

(ON)

OFF

13

HEAT-OFF-COOL-AUTO

or

HEAT-EMER-OFF-COOL-

AUTO (for heat pumps)

HEAT-OFF-COOL

or

HEAT-EMER-OFF-COOL

(for heat pumps)

14

REM SEN A

(OFF)

ON

Selects Remote Sensor A (connected to SA) if ON.

Selects:
1. one compressor on Y1.
2. two compressors on Y1, Y2.
3. one compressor on W1.

Selects HEAT anticipation adjustment.

Selects COOL anticipation adjustment.

Allows selection of HEAT and COOL or HEAT,
COOL and AUTO with SYSTEM button.
(EMER appears in sequence after HEAT if HEAT
PUMP is selected.)

Economizer option. Long Y1 cycles for cooling
with outdoor air

Selects Remote Sensor B (connected to SB) if ON.

Selects Remote Sensor C (connected to SC) if ON.

When OFF, disables local sensor if a remote sensor
is enabled.

PROGRAM

RUN

SET

and

SET

(hold for approx.

3 seconds)

TIME

DAY

TIME

(Heat Pump ONLY)

FWD

TIME

FWD

TIME

FWD

TIME

FWD

FWD

TIME

FWD

TIME

FWD

TIME

TIME

FWD

FWD

TIME

FWD

6

SET CYCLE AUX

(06)

1 to 40

9

HEAT FAN DELAY OFF

(00)

0 to 127 seconds

10

PUMP

(ON)

OFF

11

COMP LOCK

(OFF)

ON

7

COOL FAN DELAY OFF

(00)

0 to 127 seconds

8

4

4

4

4

4

6

6

6

7

6

6

4

6

6

6

6

6

FAN DELAY ON

(01)

1 to 30 seconds

Selects time delay for fan ON. Applies only to
compressor stages for heat pump or COOL.

Selects time delay for COOL fan OFF.

Selects AUXILIARY stage anticipation adjustment.
(Heat Pump ONLY)

Selects time delay for HEAT fan OFF only when
ELECT HEAT FAN (Step 3) is ON.

Fossil Fuel Kit Alternative option. Turns compressor
OFF if Auxiliary is ON for longer than one minute.
(Heat Pump 1 & 2)

Selects compressor short-cycle protection enabled
or OFF.*

TIME

(Heat Pump ONLY)

TIME

(Heat Pump ONLY)

FWD

TIME

FWD

TIME

FWD

TIME

FWD

FWD

TIME

TIME

FWD

Step

Press Button(s)

Displayed (Factory Default)

Press or to select:

COMMENTS

See

Page

NOTE: You must be in the User
Configuration Menu to enter the
Installer Menu. Press TIME

FWD

and TIME

BACK

at same time.