Specifications – Watlow Electric Controller Series D8 User Manual

Page 3

Advertising
background image

Specifications

Operator Interface

• 32-character vacuum florescent display
• 8-key keypad to access guided menus and prompts,

set values and view channel displays

• Built-in context sensitive help

Noise Rejection

• 120dB at 60Hz

Temperature Coefficient

• 40ppm/°C

Analog Inputs

• Thermocouples: user selectable type, direct connection,

linearization, reference junction compensation, reversed
and shorted thermocouple detection and upscale break
protection with output averaging.

• RTD: 2-or 3-wire, platinum, 100

Ω

@ 0°C, DIN curve.

Requires scaling resistors. See special inputs in ordering
information.

• Linear: current and voltage signals from linear transmitter

Input Range and Accuracy
Sensor

Range (°C)

Range (°F)

Accuracy

Type B

66 to 1760°C

150 to 3200°F

±4.0°C

Type E

-200 to 787°C

-328 to 1448°F

±1.0°C

Type J

-212 to 760°C

-350 to 1400°F

±1.2°C

Type K

-268 to 1371°C

-450 to 2500°F

±1.3°C

Type R

-18 to 1766°C

0 to 3210°F

±2.8°C

Type S

-18 to 1760°C

0 to 3200°F

±2.8°C

Type T

-268 to 399°C

-450 to 750°F

±1.6°C

RTD

-200.0 to 621.1°C -328.0 to 1150.0°F

±0.5°C

Note:

Accuracy @ 25°C (77°F) ambient. Valid for 10 to 100

percent of span except Type B, which is specified for
427°C (800˚F) to 1760˚C (3200˚F). RTD is for 100 per-
cent of span.

Linear Voltage and Current Inputs

Requires scaling resistors. See special inputs in ordering
information.

0-10mA

Î

(dc)

0-20mA

Î

(dc)/4-20mA

Î

(dc)

0-100mV

Î

(dc)

0-500mV

Î

(dc)

0-1V

Î

(dc)

0-5V

Î

(dc)

0-10V

Î

(dc)

0-12V

Î

(dc)

Other ranges available. Consult factory.

Input Sampling Rate at 60Hz

Each channel has the following scans per second:
• D84: 6 samples per second, (update time: 0.167 sec.)
• D88: 3 samples per second, (update time: 0.333 sec.)

Internal Measurement Resolution

• 0.006 percent, greater than 14 bits

Calibration

• Automatic zero and full scale

Digital Inputs

• TTL level used for logic, remote alarm acknowledge,

selecting recipes or jobs

• 8 inputs with 50-pin terminal board option
• 3 inputs with 18-pin terminal block option

Digital Outputs

• 18 digital outputs are available with a 50-pin terminal

board option (See Figure 4 on previous page)

• 11 outputs available with 18-pin terminal block option

(See Figure 3 on previous page)

• 1 or 2 control outputs are user assigned for each loop
• Each control output can be configured for on-off, time

proportioning or distributed zero crossing

• Outputs sink up to 60mA each at 5V

Î

(dc)

• 350mA at 5V

Î

(dc) available from onboard supply

Alarm Outputs

• Independent process and deviation alarms for each

channel

• Alarms can operate any output not used for control
• User programmable deadband, delay and startup

suppression

• Global alarm output activates when any alarm occurs
• Watchdog output indicates controller is functioning correctly

DeviceNet™ Interface

• Fully compliant with the interface guidelines for DeviceNet™

on semiconductor manufacturing tools

• Supports predefined master/slave connection set
• Group two only slave device
• Module status and network status LEDs
• Rotary baud rate and node address switches
• Hardware and software selectable baud rates: 125K, 250K

and 500K

• Hardware and software selectable node address: 0 to 63
• Supports polled I/O and explicit messaging connections
• Polled I/O response: less than 1 millisecond
• Explicit message response: less than 50 milliseconds
• EDS (Electronic Data Sheet)
• Connector: 5-pin, micro style, sealed, male
• Optically isolated CANBUS interface
• Bus plug-able while hot
• Bus mis-wire protection

Line Voltage/Power

• 15 to 24 ± 3V

Î

(dc) @ 1A (loaded) or 300mA (no load)

Agency Approvals

• UL

®

, C-UL

®

listed: UL

®

61010-1 safety requirements for

measurement, control and laboratory equipment

• CE Mark: See Declaration of Conformity for details
• ODVA conformance tested DeviceNet™

Advertising