Water piping — single-zone system, Gold cgi gas-fired water boiler — boiler manual, Diaphragm-type or bladder- type expansion tank – Weil-McLain GOLD CGI 550-110-710/0107 User Manual

Page 21: Closed-type expansion tank

Advertising
background image

Part Number 550-110-710/0107

1

GOLD CGi Gas-Fired Water Boiler — Boiler Manual

Water piping — single-zone system

4b

Diaphragm-type or bladder-

type expansion tank

(Figure 16)

1. Ensure expansion tank size will handle boiler and

system water volume and temperature. Tank must

be located in boiler return piping as close to boiler

as possible, before inlet side of circulator. See tank

manufacturer’s instructions for details.

. Install an

automatic air vent

as shown.

Figure 16

Diaphragm- or bladder-type expansion

tank — Piping to single-zone system

using diaphragm-type or bladder-type

expansion tank. See Table 6 for piping

sizes.

Figure 17

Closed-type expansion tank — Piping

to single-zone system using closed-

type expansion tank. See Table 6 for

piping sizes.

Closed-type expansion tank

(Figure 17)

1. Ensure expansion tank size will handle boiler and

system water volume and temperature. See tank

manufacturer’s instructions for details.

. Connect tank to ½” NPT tapping located behind

supply outlet, using ½” NPT piping. Pitch any

horizontal piping up towards tank 1 inch per 5 feet

of piping.

Use

Figure 16

or

Figure 17

only for single-zone systems designed for return water at least 130°F.

For systems with low return water temperature possible, such as converted gravity systems

and radiant heating systems, refer to the special piping suggestions of pages 4-9. Failure to

prevent low return water temperature to the boiler could cause corrosion of the boiler sections

or burners, resulting in severe personal injury, death or substantial property damage.

Undersized expansion tanks cause system water to be lost from relief valve and makeup water

to be added through fill valve. Eventual section failure can result.

Advertising