Prior to final approval of the installation, Limits of use, Hydro kit, version p units only – York YCSA User Manual

Page 13: Units without pack, Check

Advertising
background image

13

-10

20

30

50 (4)

342

436

-10 (3)

46 (2)

6 (1)

15

3

7

GB

- That the guarantee card has been filled

out.

- That maintenance instructions have been

given, or a periodical revision contract has
been signed.

- That operating instructions have been given

to the user.

Check:

- That voltage is always between 342 - 436 V.
- That the power supply cable section is at

least equal to the section recommended in
the corresponding wiring diagrams.

Prior to final approval of the installation

-

-

-

-

Voltage limits

Nominal at 400

DB air inlet temperature to coil

Operating cycle

Water outlet temperature

Ciclo de funcionamiento

Temp. differential between

the water outlet and

intake

Minimum °C

Maximum °C

Minimum °C

Maximum °C

Minimum °C Maximum °C

Minimum

Maximum

Cool

Heat

Cool

Heat

Cool

Heat

Frío

Heat

Model

(1) At lower water temperatures, it is advisable to use glycol type antifreeze mixtures. Minimum Tº with glycol -5 (2) IPESL - SdM - UMT - TÜV, 38°C SAQ, 40°C DUTCH. (3) -18°C with low temperature kit
(optional) in models YCSA (4) 45°C if intake air is -5°C.

YCSA

Limits of use

YCSA-H

(1) These weights correspond to the unit empty.
(2) Available static pressure, Eurovent certification (....) Cool only units.
(3) Pressure with clean filter (....) Cool only units.

Hydro Kit, version P units only

1

225 / 235

263 / 245

212 / 222

243 / 222

194

245

178

222

1 350

1 850

2,9

3,4

179

181

12

18

6

24,3

32,3

46,4

57,7

127

167

624 / 636

706 / 720

Units without pack

Start up current

A

127

167

Pressure drop, cool evaporating unit

kPa

50 / 45

37 / 55

Pressure drop, heat evaporating unit

kPa

60

55

Max. power intake unit

kW

22,9

30,4

Maz. current intake unit

A

43,5

54,3

Weight (1)

kg

568 / 580

650 / 662

W

A

l

l

kW

A

A

kg

Bar

kPa

kPa

kPa

kPa

Static pressure available nominal flow
(without filter) for cooling mode (2)

Static pressure available nominal flow
(with filter) for cooling mode (3)

Nº of pumps

Static pressure available nominal flow
(without filter) for heating mode

Static pressure available nominal flow
(with filter) for heating mode

Pump input

Pump input

Water content in unit

Expansion vessel volume

Max. pressure unit

Max. current intake unit

Start up current

Weight (1)

Max. power intake unit

Características

YCSA/YCSA-H

YCSA/YCSA-H

YCSA/YCSA-H

YCSA/YCSA-H

YCSA/YCSA-H

YCSA/YCSA-H

YCSA/YCSA-H

YCSA 50 T & TP

YCSA-H 50 T & TP

YCSA 60 T & TP

YCSA-H 60 T & TP