York CH060 User Manual

Page 13

Advertising
background image

271846-YTG-B-0208

Johnson Controls Unitary Products

13

TABLE 10: COOLING PERFORMANCE DATA - CU 25 TON VERTICAL MODELS

TABLE 11: WATER-SIDE ECONOMIZER COOLING PERFORMANCE DATA - CH 5-10 TON MODELS

CU300

25 TON

10000 CFM

45 GPM

75 GPM

EWT

EWT

65°F

85°F

105°F

65°F

85°F

105°F

EWB

EDB

TC

SC

kW

TC

SC

kW

TC

SC

kW

TC

SC

kW

TC

SC

kW

TC

SC

kW

62°F

75°F

315.1

237.0

17.53

295.4

230.9

20.29

272.1

223.0

23.95

320.9

243.4

16.74

301.3

234.2

19.37

278.7

230.4

22.78

80°F

315.1

277.9

17.53

295.4

272.5

20.29

272.1

265.9

23.95

320.9

286.2

16.74

301.3

275.8

19.37

278.7

275.5

22.78

85°F

333.6

333.6

17.63

312.8

312.8

20.41

288.1

288.1

24.11

339.8

339.8

16.84

319.0

319.0

19.49

295.1

295.1

22.94

67°F

75°F

335.8

189.6

17.71

314.8

183.2

20.50

290.4

175.9

24.21

342.0

192.5

16.92

321.6

188.2

19.58

298.2

181.7

23.03

80°F

335.8

231.9

17.71

314.8

226.0

20.50

290.4

219.3

24.21

342.0

234.5

16.92

321.6

233.3

19.58

298.2

227.2

23.03

85°F

335.8

273.9

17.71

314.8

268.8

20.50

290.4

263.0

24.21

342.0

276.8

16.92

321.6

278.0

19.58

298.2

273.0

23.03

72°F

75°F

356.4

141.1

18.09

333.8

135.3

20.83

310.2

130.1

24.58

365.1

144.1

17.30

343.4

138.8

20.01

319.2

133.2

23.40

80°F

356.4

184.7

18.09

333.8

179.5

20.83

310.2

175.5

24.58

365.1

188.7

17.30

343.4

183.9

20.01

319.2

178.8

23.40

85°F

356.4

228.5

18.09

333.8

223.6

20.83

310.2

221.0

24.58

365.1

232.9

17.30

343.4

228.9

20.01

319.2

224.6

23.40

UNIT

Air @ 80°F EDB, 67°F EWB

Water

Capacity [MBH]

CFM

PD [in WG]

Flow [GPM]

PD [PSI]

EWT [°F]

Total

Sensible

CH060

2000

0.16

9

1.4

45

50.8

39.9

55

31.4

31.4

15

3.8

45

64.5

45.0

55

35.0

35.0

CH096

3200

0.14

15

1.4

45

87.4

66.5

55

52.7

52.7

24

3.4

45

107.1

73.8

55

60.5

57.0

CH120

4000

0.21

18

1.9

45

104.6

80.3

55

63.0

63.0

30

5.2

45

127.3

88.6

55

68.9

68.9


NOTE:

1. All economizer coils are 3R, 10 FPI, aluminum fins with copper tubes and headers.

2. For total system waterside pressure drop, add condenser pressure drop and waterside economizer coil pressure drop.

Advertising
This manual is related to the following products: