13 electrical data - df072 belt drive, W/powered conv. outlet, 14 electrical data - df072 direct drive – York DF 072 User Manual

Page 13

Advertising
background image

254599-YTG-C-0807

Unitary Products Group

13

TABLE 13: ELECTRICAL DATA - DF072 BELT DRIVE W/POWERED CONV. OUTLET

MODEL

TONNAGE

VOLTAGE

COMPRESSORS

OD FAN
MOTOR

FLA

ID

BLOWER

MOTOR

FLA

CONV

OUTLET

FLA

ELECTRIC HEATER

MODEL NO.

HEATER

KW

HEATER

AMPS

MIN.

CIRCUIT

AMPACITY

(AMPS)

MAX. FUSE/

BRKR

1

SIZE

(AMPS)

RLA

EACH

LRA

EACH

DF072

(6.0)

208-3-60

20.7

156.0

2.3

5.2

10.0

None

-

-

43.4

60

2CE04510525

2

4

11.1

43.4

60

2CE04510725

2

5.6

15.5

43.4

60

2CE04511025

8

22.2

46.8

60

2CE04511525

11.9

33.0

60.3

70

2CE04512025

15.9

44.1

74.2

80

2CE04513025

22.2

61.6

96

100

230-3-60

20.7

156.0

2.3

5.2

10.0

None

-

-

43.4

60

2CE04510525

2

5.3

12.7

43.4

60

2CE04510725

2

7.5

18.0

43.4

60

2CE04511025

10.6

25.5

50.9

60

2CE04511525

15.9

38.2

66.8

70

2CE04512025

21.2

51.0

82.7

90

2CE04513025

29.6

71.2

108

110

460-3-60

10.0

75.0

1.3

2.6

5.0

None

-

-

21.4

30

2CE04510746

2

6.8

8.2

21.4

30

2CE04511046

2

10.1

12.1

24.7

30

2CE04511546

2

13.6

16.4

29.9

30

2CE04512046

2

19.5

23.5

38.8

40

2CE04513046

2

28.8

34.6

52.8

60

575-3-60

8.2

54.0

1.3

2.0

4.0

None

-

-

17.3

25

2CE04511058

10.6

10.2

20.2

25

2CE04511558

15.9

15.3

26.6

30

2CE04512058

21.2

20.4

33

35

2CE04513058

30.4

29.3

44.1

45

1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block

accessories 2FB04700825 and 2FB04700846 are available for field installation.

TABLE 14: ELECTRICAL DATA - DF072 DIRECT DRIVE W/POWERED CONV. OUTLET

MODEL

TONNAGE

VOLTAGE

COMPRESSORS

OD FAN
MOTOR

FLA

ID

BLOWER

MOTOR

FLA

CONV

OUTLET

FLA

ELECTRIC HEATER

MODEL NO.

HEATER

KW

HEATER

AMPS

MIN.

CIRCUIT

AMPACITY

(AMPS)

MAX. FUSE/

BRKR

1

SIZE

(AMPS)

RLA

EACH

LRA

EACH

DF072

(6.0)

208-3-60

20.7

156.0

2.3

10.6

10.0

None

-

-

48.8

60

2CE04510525

2

4.0

11.1

48.8

60

2CE04510725

2

5.6

15.5

48.8

60

2CE04511025

8.0

22.2

53.5

60

2CE04511525

11.9

33.0

67.0

70

2CE04512025

15.9

44.1

80.9

90

2CE04513025

22.2

61.6

102.8

110

230-3-60

20.7

156.0

2.3

10.6

10.0

None

-

-

48.8

60

2CE04510525

2

5.3

12.7

48.8

60

2CE04510725

2

7.5

18.0

48.8

60

2CE04511025

10.6

25.5

57.6

60

2CE04511525

15.9

38.2

73.6

80

2CE04512025

21.2

51.0

89.5

90

2CE04513025

29.6

71.2

114.8

125

1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block

accessories 2FB04700825 and 2FB04700846 are available for field installation.