Start-up – York SUNLINE 2000 D2CG 072 User Manual

Page 16

Advertising
background image

The limit switch operates when a high temperature
condition, caused by inadequate supply air flow, occurs
shutting down the ignition control and closing the main gas
valve.

2. Centrifugal Switch (CS-36). If the draft motor should fail, the

centrifugal switch attached to the shaft of the motor
prevents the ignition control and gas valve from being
energized.

3. Redundant Gas Valve. This valve is an integral part of the

main gas valve and is located up stream of the main gas
valve. Should the main gas valve fail in the open position
the redundant valve serves as a back up and shuts off the
flow of gas.

4. Flame Sensor Rod. This sensor rod is located on the far

side of the carryover tube. If the ignition control does not
receive a signal from the flame sensor indicating that the
pilot flame has ignited properly, the main gas valve will not
open. If the flame sensor fails to detect the pilot flame during

operation of the main burners, a signal is sent to the ignition
control to close the main gas valve.

5. Rollout Switch. This switch is located in the burner

vestibule. In the event of a sustained main burner flame
rollout, it shuts off the ignition control and closes the main
gas valve.

6. Auxiliary Limit Switch. This control is located inside the heat

exchanger compartment and is set to open at 180

°

F. It is a

manual reset switch. If the auxiliary limit switch trips, then
the primary limit switch has not functioned properly.
Replace the primary limit switch.

HEAT ANTICIPATOR SETPOINTS

The anticipator must be set correctly. Too high of a setting will
result in longer heat cycles and a greater temperature swing in
the conditioned space.

Reducing the value below the correct setpoint will give shorter
“ON” cycles and may result in the lowering of the temperature
within the conditioned space.

PRE-START CHECK LIST

Complete the following checks before starting the unit.

1. Check the type of gas being supplied. Be sure that it is the

same as listed on the unit nameplate.

2. Make sure that the vent and combustion air hoods have

been properly installed.

Units

(Tons)

Capacity, MBH

Limit Control

Opens,

°

F

Input

Output

3
4
3
4
5
5
6
6

50
75

100
125
100
125
100
125

40
60
79
99
79
99
79
99

165
165
165
165
165
165
165
165

TABLE 16 - LIMIT CONTROL SETTING

Gas Valve

Anticipator Setpoint

Honeywell VR8204M

0.60 amp

White-Rodgers 36E36

0.54 amp

START-UP

OPERATING INSTRUCTIONS

CAUTION: This furnace is equipped with an intermittent pilot

and automatic re-ignition system. DO NOT attempt
to manually light the pilot.

TO LIGHT PILOT AND MAIN BURNERS:

1. Turn “off” electric power to unit.

2. Turn room thermostat to lowest setting.

3. Turn gas valve knob to “on” position.

4. Turn “on” electric power to unit.

5. Set room thermostat to desired temperature.

(If thermostat “set” temperature is above room temperature,
pilot burner ignition will occur and, after an interval to prove
pilot flame, main burners will ignite).

TO SHUT DOWN:

1. Turn “off” electric power to unit.

2. Depress knob of gas valve while turning to “off” position.

POST-START CHECK LIST (GAS)

After the entire control circuit has been energized and the
heating section is operating, make the following checks:

1. Check for gas leaks in the unit piping as well as the supply piping.

2. Check for correct manifold gas pressures. See “Checking

Gas Input”.

3. Check the supply gas pressure. It must be within the limits

shown on rating nameplate. Supply pressure should be
checked with all gas appliances in the building at full fire.
At no time should the standby gas line pressure exceed 13",
nor the operating pressure drop below 4.5" for natural gas
units. If gas pressure is outside these limits, contact the
local gas utility for corrective action.

MANIFOLD GAS PRESSURE ADJUSTMENT

Small adjustments to the high-fire gas flow may be made by
turning the pressure regulator adjusting screw on the automatic
gas valve. Refer to Figure 11.

Adjust as follows:

1. Remove the cap on the regulator. (High Fire adjusting

screw on valve).

2. To decrease the gas pressure, turn the adjusting screw

counterclockwise.

3. To increase the gas pressure, turn the adjusting screw

clockwise.

NOTE: Check the unit data plate for the proper manifold pres-

sure and orfice size of the furnace.

PILOT ADJ.
(UNDER
SCREW)

“ON”-"OFF"
CONTROL
HIGH FIRE ADJ.
(UNDER SCREW)

Honeywell
VR8204M

“ON”-"OFF" CONTROL

PRESSURE REGULATOR

MANIFOLD ADJUST. SCREW

1/2-14 NPT (OUTLET)

White-Rodgers
36E36

PILOT ADJ.
(UNDER
SCREW)

FIG. 11 - GAS VALVES

530.18-N8Y

16

Unitary Products Group

Advertising
This manual is related to the following products: