Installation procedure – Zenith HYDROTAP 37691 User Manual

Page 7

Advertising
background image

Zenith Hydro Tap Installation and Operating Instructions - 81467 - February 2005

Page 7 of 20

Step D - Connecting the water supply (all models)

To prevent sediment from entering the Zenith HydroTap at connection, flush water
through the supply line thoroughly before connection to the Zenith HydroTap.
Open the access door and check that the filter is in place and secure. Connect
the water supply to the undersink unit using the attached flexible hose.
Turn on water and check for leaks. If no leaks are evident turn the poer on.

Step E - Testing and commissioning (all models except boiling only HT models)

Filter Flush Mode (filtered models only)

The display screen will show which model you have.

Have a bucket or similar container (not supplied) at the ready to
hold a quantity of water that is ejected while the Filter Flush Mode is in
operation. Open the filter access door on the front of the HydroTap and the
filter cartridge will be exposed. Located to the rear RHS of the cartridge is a
fixed flush line, approx 600mm long and the flush line stop cock. Place the
free end of the flush line into the bucket or container (not supplied).

Turn “ON” both water and electricity supplies and open the flush line stop
cock. The display will show Filter Flush Mode. To activate press adjust

∧. Run

at least 7.5 Ltrs of water through to activate the filter membrane. Press the
adjust

∧ button again to stop the Filter Flush Mode. Turn OFF the Filter Flush

stop cock and re-locate the tube and stop cock in the filter compartment.
Turning OFF the Filter Flush Mode puts the HydroTap into calibration mode.
Press adjust

∧ to start calibration.The element will now cycle On and heat the

water to 95ºC maintaining it at that temperature for a short stabilization
period.

Once stabilized, the element will cycle On, bring the water to boiling point
and hold it there for a short period.

The unit now carries out a self calibration function to ensure correct
temperatures are maintained. During this period the Red LED on the Tap Head
assembly flashes slowly until the calibration function is complete.

Once this step is complete (approx 5 minutes) the unit will default to normal
operation.

When starting, both Boiling and Chilled cycles activate similtaneously after
calibration has taken place, the descriptions below indicate what happens
during each cycle.

Boiling
The unit is now running in normal operating mode. The Red LED will flash until
usable temperature is reached.

Before using the HydroTap wait 5 minutes after this point to allow adequate fill
time. The unit is now ready for use. Test water delivery from the tap and check
for appropriate temperatures. Use cable clips to tidy and secure wiring.

Chilled
When water and power is turned On, the Blue LED flashes slowly on the Tap
Head assembly. The compressor activates and water begins to fill the chiller
tank at the prescribed rate. When the water is chilled to 10ºC the Blue LED on
the Tap Head assembly stops flashing and stays illuminated. The compressor
continues to chill down to 5º after which it will cycle Off.

Ensure that the clock matches your local time. If not refer to page 15 “Set
time”. If Energy Saver Settings are required, the instructions for installing
these are described on on page 11 “Setting the Energy Saver Timer”.

Installation procedure

continued

Boiling Water Lever

Chilled Water Lever

Red Light

White Light

Blue Light

Boiling Filter Status Chilled

Use these buttons to
scroll through the menu

Use these buttons to

activate and de-activate

the program selected

Advertising