Table 34: minimum clearances – York DJ 060 User Manual

Page 39

Advertising
background image

036-21687-002-A-1105

Unitary Products Group

39

FIGURE 7 -

UNIT DIMENSIONS (REAR VIEW)

FIGURE 8 -

DISCONNECT/BLOWER ACCESS
LOCATION

TABLE 33: UTILITIES ENTRY

HOLE

OPENING SIZE (DIA.)

USED FOR

A

7/8” KO

1

Control Wiring

2

Side

Bottom

B

2” KO1

Power Wiring

Side

Bottom

C

1-5/8” KO

Gas Piping (Front)

D

1-1/2” KO

Gas Piping (Bottom)

DISCONNECT SWITCH LOCATION

AND MOTOR ACCESS PANEL FOR

UNIT WITH “BELT-DRIVE” OPTION

CONTROL BOX
ACCESS

A,B
WIRING ENTRY
(See Detail “B”)

MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the

blower housing inside
the blower compartment)

FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION

BLOWER MOTOR
ACCESS

FILTER
ACCESS

DOT PLUGS

1. Opening in the bottom to the unit can be located by the

side in the insulation.

2. Do not remove the 2” knockout ring.

TABLE 34: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

24” (Cooling/Electric Heat)

32” (Gas Heat)

Rear

12” (Less Economizer)

36” (With Economizer or Fixed

Air/Motorized Damper)

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)

Right Side (Cond. Coil)

24”

Below Unit

1

1. Units may be installed on combustible floors made

from wood or class A, B, or C roof covering material.

0”

Above Unit

2

2. Units must be installed outdoors. Overhanging struc-

tures or shrubs should not obstruct condenser air dis-
charge outlet.

72” (For

Condenser Air Discharge)