246653-YTG-E-0108

Johnson Controls Unitary Products

11

SELECTION PROCEDURE

GIVEN:

Required Cooling Capacity

460,000 Btuh

Required Sensible Cooling

390,000 Btuh

Required Heating (Gas)

320,000 Btuh

Entering Air on Evaporator

83° F DB/ 67° F WB

Outside Design Temperature

95° F

Supply Fan CFM

13,000 CFM

External Static Pressure

1.25 IWG

Electrical Supply Voltage

460-3-60

Economizer Required

2” Throw Away Filters

Constant Volume

SELECT UNIT:

1.

Determine nominal tons:

460,000 / 12,000 = 38.33 Tons
Thus, a nominal 40 ton unit is selected.

2.

Reference Cooling Capacity Table for a 40 ton unit with
standard evaporator coil.

a.

Locate the table for a standard evaporator coil with
95° F air on the condenser.

b.

Enter table at 13,000 CFM and 67°F WB air on
evaporator

c.

Trace to 83° F Entering Dry Bulb column.

d.

Read 493 MBH total capacity and 403 MBH sensi-
ble capacity.

The 40 ton unit will meet the cooling requirements. From
the nomenclature, the unit will be a Y34. Choose the
appropriate configuration for the next digit. Assuming
bottom return and supply, the fourth digit would be an
“A,” making the model Y34A.

3.

Find Gas Heating Capacity Table.

a.

Trace down Output column.

b.

Find output which exceeds 320,000 Btuh require-
ment. The N5 option gives 426 MBH output.

c.

Ensure that it is offered in the Y34 unit. Read option
model as N5.

From the basic nomenclature, the model now becomes
Y34AN5. Add voltage code of “4” for 460-3-60. Nomen-
clature becomes Y34AN54.

SELECT FAN SPEED AND HORSEPOWER
REQUIREMENTS OF SUPPLY AIR FAN

1.

Find Supply Air Performance Tables for the 40 ton unit.

a.

Check footnotes and make necessary additions or
deductions to static resistance of ductwork:

Ductwork static resistance 1.25

IWG

Economizer static resistance addition
(interpolate) =.25 IWG + Gas Heat (High) =

0.5 IWG

Total Static Resistance

2.0 IWG

b.

Enter Fan Performance Table at 13,000 CFM and
2.0 IWG static pressure:

RPM = 690
BHP = 10.7

NOTE: Either a Class I or Class II blower could be used.

c.

Enter the Fan Motor Drive Tables. Selecting a 15 hp
motor allows (service factor of 1.5) for a maximum
operating BHP greater than the 10.7 BHP require-
ment.

SIZE OVERCURRENT PROTECTION DEVICE AND
DETERMINE CIRCUIT AMPACITY

1.

Find electrical tables for the basic 40 ton unit.

a.

Enter table for 460-3-60 voltage.

b.

Find 15 hp in the Supply Air Fan column.

c.

Trace to Minimum Circuit Ampacity column - read
104.

d.

Trace to Max. Fuse/Breaker Size column - read 110.

e.

Size wire and overprotection device accordingly.

f.

Check all footnotes.

TABLE 2: REFRIGERANT CHARGE

UNIT (T

ONS

)

MODEL

TYPE

F

ACTORY

/ F

IELD

C

HARGED

C

HARGE

SYS #1

SYS #2

SYS #3

SYS #4

25

wo/HGBP

R22

Factory

25 lb. / 8 oz.

26lb / 0oz

-

-

25

w/HGBP

R22

Factory

26 lb. / 0 oz.

26 lb. / 0oz

-

-

30

wo/HGBP

R22

Factory

13 lb. / 4 oz.

13 lb. / 8 oz.

13 lb. / 8 oz.

-

30

wo/HGBP

1

R22

Factory

14 lb. / 6 oz.

14 lb. / 10 oz.

14 lb. / 10 oz.

-

30

w/HGBP

R22

Factory

14 lb. / 0 oz.

13 lb. / 8 oz.

13 lb. / 8 oz.

-

30

w/HGBP

1

R22

Factory

15 lb. / 2 oz.

14 lb. / 10 oz.

14 lb. / 10 oz.

-

40

wo/HGBP

R22

Factory

15 lb. / 5 oz.

15 lb. / 4 oz.

15 lb. / 5 oz.

15 lb. / 15 oz.

40

w/HGBP

R22

Factory

15 lb. / 13 oz.

15 lb. / 4 oz.

15 lb. / 5 oz.

15 lb. / 15 oz.

1.

With high capacity evaporator coil.

Advertising
This manual is related to the following products:

Y34, Y32