Wiring diagram - wye-delta start, Wiring diagram, Wye-delta start – York MILLENNIUM YCAS0230 User Manual

Page 14

Advertising
background image

YORK INTERNATIONAL

14

WIRING DIAGRAM

WYE-DELTA START

NOTES:
1. Field wiring to be in accordance with the current

edition of the National Electrical Code as well as all

other applicable codes and specifications.

2. Numbers along the right side of a diagram are line

identification numbers. The numbers at each line

indicate the line number location of relay contacts.

An unlined contact location signifies a normally closed

contact. Numbers adjacent to circuit lines are the

circuit identification numbers.

3. Any customer supplied contacts must be suitable

for switching 24VDC. (Gold contacts recom-

mended.) Control Wiring must not be run in the same

conduit with any line voltage wiring.

4. To cycle unit on and off automatically with contact

shown, install a cycling device in series with the

flow switch (FSLW). See Note 3 for contact rating

and wiring specifications. Also refer to cautions on

the following page.

5. To stop unit (Emergency Stop) with contacts other

than those shown, install the stop contact between

5 and 1. If a stop device is not installed, a jumper

must be connected between terminals 5 and 1. De-

vice must have a minimum contact rating of 100VA

at 115 volts A.C.

6. Alarm contacts are for annunciating alarm/unit mal-

function. Contacts are rated at 115V, 100VA, resis-

tive load only, and must be suppressed at load by

user.

7. See Installation, Operation and Maintenance Manual

when optional equipment is used.

8. Control panel to be securely connected to earth

ground.

9. Us 2KVA transformer in optional transformer kit un-

less there are optional oil separator sump heaters

which necessitates using a 3KVA transformer.

FIG. 1 – ELEMENTARY DIAGRAM – WYE-DELTA START

LEGEND

Transient Voltage Suppression

Terminal Block for Customer Connections

Terminal Block for Customer Low Voltage
(Class 2) Connections. See Note 2

Terminal Block for YORK Connections Only

Wiring and Components by YORK

Optional Equipment

Wiring and/or Components by Others

T S

LD03226

LD03227