Troubleshooting – York DM150 User Manual

Page 50

Advertising
background image

127408-YIM-B-0606

50

Unitary Products Group

TROUBLESHOOTING

PREDATOR

®

FLASH CODES

Various flash codes are utilized by the unit control board
(UCB) to aid in troubleshooting. Flash codes are
distinguished by the short on and off cycle used
(approximately 200ms on and 200ms off). To show normal
operation, the control board flashes a 1 second on, 1 second
off "heartbeat" during normal operation. This is to verify that
the UCB is functioning correctly. Do not confuse this with an
error flash code. To prevent confusion, a 1-flash, flash code
is not used.

Alarm condition codes are flashed on the UCB lower left Red
LED, See Figure 30. While the alarm code is being flashed, it
will also be shown by the other LEDs: lit continuously while
the alarm is being flashed. The total of the continuously lit
LEDs equates to the number of flashes, and is shown in the
table. Pressing and releasing the LAST ERROR button on
the UCB can check the alarm history. The UCB will cycle
through the last five (5) alarms, most recent to oldest,
separating each alarm flash code by approximately 2
seconds. In all cases, a flashing Green LED will be used to
indicate non-alarm condition.

In some cases, it may be necessary to "zero" the ASCD for
the compressors in order to perform troubleshooting. To reset
all ASCDs for one cycle, press and release the UCB TEST/
RESET button once.

Flash codes that do and do not represent alarms are listed in
Table 52.

Troubleshooting of components may require open-
ing the electrical control box with the power con-
nected to the unit. Use extreme care when
working with live circuits!
Check the unit name-
plate for the correct line voltage and set the voltme-
ter to the correct range before making any
connections with line terminals.

When not necessary, shut off all electric power to the
unit prior to any of the following maintenance proce-
dures so as to prevent personal injury.

Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dan-
gerous operation which could cause injury to person
and/or damage unit components. Verify proper oper-
ation after servicing.

TABLE 52: UNIT CONTROL BOARD FLASH CODES

FLASH CODE

DESCRIPTION

GREEN

LED

16

RED

LED

8

RED

LED

4

RED

LED

2

RED

LED

1

On Steady

This is a Control Failure

-

-

-

-

-

1 Flash

Not Applicable

-

-

-

-

-

2 Flashes

Control waiting ASCD

*

*.

Non-alarm condition.

Flashing

Off

Off

On

Off

3 Flashes

HPS1 Compressor Lockout

Off

Off

Off

On

On

4 Flashes

HPS2 Compressor Lockout

Off

Off

On

Off

Off

5 Flashes

LPS1 Compressor Lockout

Off

Off

On

Off

On

6 Flashes

LPS2 Compressor Lockout

Off

Off

On

On

Off

7 Flashes

FS1 Compressor Lockout

Off

Off

On

On

On

8 Flashes

FS2 Compressor Lockout

Off

On

Off

Off

Off

9 Flashes

Ignition Control Locked Out / Ignition Control Failure

Off

On

Off

Off

On

10 Flashes

Compressors Locked Out on Low Outdoor Air Temperature

1

Flashing

On

Off

On

Off

11 Flashes

Compressors locked out because the Economizer is using free

Cooling

1

Flashing

On

Off

On

On

12 Flashes

Unit Locked Out due to Fan Overload Switch Failure

Off

On

On

Off

Off

13 Flashes

Compressor Held Off due to Low Voltage

1

Flashing

On

On

Off

On

14 Flashes

EEPROM Storage Failure

Off

On

On

On

Off

OFF

No Power or Control Failure

Off

Off

Off

Off

Off