York YHJF18 User Manual

Page 17

Advertising
background image

510667-YTG-A-0409

Johnson Controls Unitary Products

17

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

COOLING PERFORMANCE DATA

CONDENSING UNIT MODEL NO. YHJF48S41S1

INDOOR COIL MODEL NO.

F6FP060

CONDENSING

ENTERING AIR

TEMPERATURE

IDCFM

1400

1600

1800

ID

DB

(°F)

80 80

75

80

80

80 80 75

80

80 80 80

75 80 80

ID

WB

(°F)

57 62 62 67 72 57 62 62 67 72 57 62 62 67 72

65

T.C.

46.3

48.5

48.5

53.1

57.3

48.0

50.1

49.9

53.5

58.0

49.8

51.6

51.4

53.9

58.7

S.C.

46.3

42.2

35.8

35.4

29.2

48.0

45.7

38.1

36.7

29.9

49.8

49.3

40.4

38.0

30.6

KW

2.7

2.7

2.7

2.8

2.7

2.8

2.8

2.8

2.8

2.8

2.9

2.9

2.9

2.9

2.9

75

T.C.

44.4

46.1

46.1

50.7

55.0

46.2

47.4

47.3

51.3

55.8

48.0

48.7

48.5

51.8

56.5

S.C.

44.4

41.2

34.8

34.4

28.2

46.2

44.2

37.0

36.0

29.0

48.0

47.1

39.2

37.5

29.8

KW

3.0

3.0

3.0

3.0

3.1

3.1

3.1

3.1

3.1

3.2

3.2

3.2

3.2

3.2

3.2

85

T.C.

42.4

43.6

43.6

48.3

52.7

44.3

44.7

44.7

49.0

53.5

46.2

45.7

45.7

49.8

54.3

S.C.

42.4

40.2

33.7

33.5

27.1

44.3

42.6

35.8

35.3

28.0

46.2

45.0

38.0

37.0

29.0

KW

3.3

3.3

3.3

3.3

3.4

3.4

3.4

3.4

3.4

3.5

3.5

3.5

3.5

3.6

3.6

95

T.C.

40.5

41.1

41.2

45.9

50.5

42.5

42.0

42.0

46.8

51.3

44.4

42.8

42.8

47.7

52.1

S.C.

40.5

39.2

32.7

32.6

26.0

42.5

41.0

34.7

34.6

27.1

44.4

42.8

36.8

36.5

28.2

KW

3.7

3.7

3.7

3.6

3.8

3.8

3.8

3.8

3.8

3.9

3.9

3.9

3.9

3.9

4.0

105

T.C.

37.9

38.3

37.6

42.7

47.5

39.7

39.5

38.5

43.5

48.2

41.5

40.7

39.3

44.3

48.8

S.C.

37.9

37.4

31.1

31.4

24.8

39.7

39.1

33.2

33.3

25.9

41.5

40.7

35.3

35.3

26.9

KW

4.0

4.0

4.0

4.1

4.2

4.2

4.2

4.1

4.2

4.3

4.3

4.3

4.2

4.3

4.4

115

T.C.

35.2

35.5

34.0

39.5

44.6

36.9

37.1

34.9

40.2

45.1

38.7

38.7

35.8

41.0

45.5

S.C.

35.2

35.5

29.6

30.1

23.6

36.9

37.1

31.7

32.1

24.7

38.7

38.7

33.9

34.1

25.7

KW

4.4

4.4

4.4

4.6

4.6

4.6

4.6

4.5

4.7

4.7

4.7

4.7

4.6

4.7

4.8

125

T.C.

32.6

32.7

30.4

36.3

41.7

34.2

34.7

31.3

37.0

42.0

35.8

36.6

32.2

37.7

42.3

S.C.

32.6

32.7

28.0

28.8

22.4

34.2

34.7

30.2

30.9

23.5

35.8

36.6

32.2

32.9

24.5

KW

4.8

4.8

4.8

5.0

5.1

5.0

5.0

4.9

5.1

5.1

5.1

5.1

5.0

5.2

5.2

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

AHX60

1.00

0.99

1.04

MV20D

FC/MC62D

1.00

1.01

1.04

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

T*(8,L)X*C16

FC/MC62D

1.00

1.01

1.08

T*(8,L)X*C20

FC/MC62D

1.00

1.01

1.08

T*9X*C16

FC/MC62D

1.00

1.00

1.08

T*9X*C20

FC/MC62D

1.00

1.01

1.08

T*9X*D20

FC/MC62D

1.00

1.00

1.08

Y*(8,L)(C,V)*C16

FC/MC62D

1.00

1.00

1.08

Y*(8,L)(C,V)*C20

FC/MC62D

1.00

1.00

1.08

Y*9(C,V)*C16

FC/MC62D

0.99

1.00

1.07

Y*9(C,V)*C20

FC/MC62D

0.99

0.99

1.07

Y*9(C,V)*D20

FC/MC62D

0.99

0.99

1.07

Advertising