Installation – York E2FB120 User Manual

Page 3

Advertising
background image

LIMITATIONS

These units must be installed in accordance with all national

and local safety codes. If no local codes apply, installation must

conform with the appropriate national codes. See Table 1 for

unit application data. Units are designed to meet National

Safety Code Standards.If components are to be added to a unit

to meet local codes, they are to be installed at the dealer's

and/or the customer's expense.

LOCATION

Use the following guidelines to select a suitable location for

these units.
1. The outdoor units must be installed outside the building.

The outdoor fans are the propeller type and are not suitable

for use with duct work.

2. The outdoor and indoor units should be installed as close

together as possible and with a minimum number of bends

in the refrigerant piping. Refer to REFRIGERANT PIPING

for additional information.

3. The outdoor unit should not be installed beneath windows

or between structures where normal operating sounds may

be objectionable.

WARNING: The outdoor unit should not be installed in an area

where mud and/or ice could cause personal injury.

Remember that condensate will drip from the un-

derside of the unit coils during heat and defrost cy-

cles and that this condensate will freeze when the
temperature of the outdoor air is below 32
°F.

4. All units require certain clearances for proper operation and

service. Refer to General Installation Form 55.70-N1 for

additional guidelines.

On either roof top or ground level installations, rubber padding

can be applied between the base rails and their supports to

lessen any transmission of vibration.

ROOF-TOP LOCATIONS

Be careful not to damagethe roof. Consultthe buildingcontrac-

tor or architectif the roof is bonded.Choosea locationwith ade-

quate structural strength to support the unit.
The unit must be mounted on solid level supports. The sup-

ports can be channel iron beams or wooden beams treated to

reduce deterioration.
A minimum of two (2) beams are required to support each unit.

The beams should: (1) Be positioned perpendicular to the roof

joists. (2) Extend beyond the dimensions of the unit to

distribute the load on the roof, (3) Be capable of adequately

supporting the entire unit weight. Refer to Figure 1 and Table 2

for load distribution and weights.
Thesebeamscan usuallybe set directlyon the roof. Flashingis

not required.
NOTE: On bonded roofs, check for special installation re-

quirements.

GROUND LEVEL LOCATIONS

The units must be installed on a substantial base that will not

settle. Any strain on the refrigerant lines may cause a refriger-

ant leak. Aone-piececoncrete slab with footers that extend be-

low the frost line is recommended. The slab should not be tied

to the building foundationbecause noise and vibration will tele-

graph into the building.
A unit can also be supported by concrete piers. These piers

should: (1) extend below the frost line, (2) be located under the

unit's four corners and (3) be sized to carry the entire unit

weight. Refer to Figure 1 and Table 2 for the center of gravity

and unit weight.
A gravel bed or some other means of handling the condensate

that will drop from the underside of the unit coil during the heat-

ing and defrost cycles may have to be provided.
CAUTION: Care should be taken to protect the unit from tam-

pering and unauthorized persons from injury.

Screws on access panels will prevent casual tam-

pering. Additional safety precautions such as

fences around the unit or locking devices on the

panels may be advisable. Check local authorities

for safety regulations.

RIGGING AND HANDLING

Exercise care when moving the unit. Do not remove any pack-

aging until the unit is near the place of installation.
Rig the unit by attaching nylon straps with hooks to the lifting

holes provided in the base rails. Spreaders, whose length ex-

ceeds the largest dimension across the unit, MUST be used

across the top of the unit if the rigging height above the top of

the unit is less than 5 feet. See Figure 2.
WARNING: Do not use straps under the unit or through the fork

lift slots for lifting purposes. Sharp metal edges

can damage the straps and could result in per-

sonal injury or equipment damage.

BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT

IS DISTRIBUTED EQUALLY ON THE STRAPS SO THAT IT

WILL LIFT EVENLY.

Unitary Products Group

3

035-15410-002-B-0404

INSTALLATION

Voltage Variation (Min/Max.)

1

208/230-3-60

460-3-60

380/415-3-50

187/252

432/504

342/456

Air Temperature on OUTDOOR coil,

°F

Minimum

Maximum

Cool

Heat

Cool

Heat

40db

0db

2

115db

75db

Air Temperature on INDOOR coil,

°F

Minimum

Maximum

Cool

Heat

Cool

Heat

57wb

50db

3

72wb

80db

Maximum Line Lengths - 125 ft.

1

Rated in accordance with ARI Standard 110, utilization range “A”.

2

Below 0°F, the control system stops the compressor and allows the electric heat accessory to

cycle at its standby capacity.

3

Operation below this temperature is permissible for a short period of time when a unit is

required to heat the conditioned space up to 50°F.

TABLE 1

- UNIT APPLICATION DATA

FRONT

APPROXIMATE

CENTER OF GRAVITY

BACK

(COIL

END)

A

C

D

B

Unit

Dim. (Iin.)

A

B

C

D

7-1/2 Ton

42-3/4

31-3/4

21-1/4

11-1/2

10 Ton

70-1/8

32

30-3/4

15-1/8

FIG. 1 - CENTER OF GRAVITY

Advertising
This manual is related to the following products: