Remote control panel – Xantrex Technology 2500 User Manual

Page 7

Advertising
background image

90-0115-00

10/97 Fltman.pm65

REMOTE CONTROL PANEL

Volts bargraph will stop indicating battery
voltage and display the dip switch settings.
It will return to indicating battery voltage
only after the unit has been reset.

DC Amps Bargraph

These LEDs approximate DC input

current in inverter mode and DC output
current in battery charger mode. Two
ranges are used -- below 50 Amps each
segment represents a 10 Amp increment,
above 50 Amps each segment represents a
20 Amp increment. Above 130 Amps, a
flashing LED segment indicates the value
displayed plus 100 Amps (flashing 50 LED
is equal to 50 + 100 or 150 Amps DC).

If a shutdown occurs, the DC Amps

bargraph will stop indicating DC Amps and
will indicate the type of problem . Each LED
segment indicates a different problem as
described in the troubleshooting section on
page 34.

Remote Power Switch

The switch on the remote is used to

control the inverter and can also be used to
control the battery charger function. When
a remote control is used, the power switch
on the inverter should be left in the OFF
position.

System Status LEDs

These 4 LEDs monitor the system as

described in the table on page 10.

DC Volts Bargraph

These LEDs indicate battery voltage as

measured inside the unit. Each LED seg-
ment indicates .5 Volts. If an overload
occurs and the unit shuts down, the DC

An optional remote control panel is

available which offers several features not
found on the unit. The remote control panel
provides LED bargraphs which show system
status, battery voltage, and DC Amps in
both inverter and charge modes. These
bargraphs can also display dip switch posi-
tions and shut down conditions.

7