66307-YIM-B-0606

Unitary Products Group

9

LOCATION

Use the following guidelines to select a suitable location for
these units:

1.

Unit is designed for outdoor installation only.

2.

Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit
on either north or east side of building.

3.

Suitable for mounting on roof curb.

4.

For ground level installation, use a level concrete slab
with a minimum thickness of 4 inches (102 mm). The
length and width should be at least 6 inches (152 mm)
greater than the unit base rails. Do not tie slab to the
building foundation.

5.

Roof structures must be able to support the weight of the
unit and its options/accessories. Unit must be installed
on a solid, level roof curb or appropriate angle iron
frame.

6.

Maintain level tolerance to 1/2” (13 mm) across the entire
width and length of unit.

FIGURE 4 -

PREDATOR

®

COMPONENT LOCATION

Tool-less door
latch

Side entry

power and control
wiring knockouts

Simplicity™ Control
board w/screw con-
nector for T-stat wir-
ing and network
connection.

Disconnect location
(optional disconnect switch)

Filter access (2” throw-away)

Roof curbs in eight- and fourteen-inch
heights. Roof curbs for transitioning from
York Sunline™ footprint to the BP Series
footprint are also available.
(field-installed accessory)

Slide-out drain pan
with steel 3/4” FPT

connection

Compressor #1 access (high-
efficiency compressor)

Belt-drive
blower motor

Filter drier (solid
core)

Condenser
section

Slideout motor
& blower
assembly for
easy access
adjustment &
service

Base rails w/fork-
lift slots (3 sides)
and lifting holes)

Compressor #2
access (high-
efficiency com-
pressor)

Terminal block for
hi-voltage connection

Second model name-
plate inside hinged
access panel

TABLE 1: UNIT TEMPERATURE LIMITATIONS

Temperature

Min.

Max.

Wet Bulb Temp

°F (°C) of Air on Evap Coil

57 (14)

72 (22)

Dry Bulb Temp

°F (°C) of Air on Cond Coil

0 (-18)

125 (52)

TABLE 2: UNIT VOLTAGE LIMITATIONS

Power Rating

*

*.

Utilization range “A” in accordance with ARI Standard
110.

Minimum

Maximum

380/415-3-50

342

456