York GHD User Manual

Page 5

Advertising
background image

036-21145-003 Rev. A (0403)

Unitary Products Group

5

STATIC PRESSURE VS. AIRFLOW (BASED ON WET COIL)

(T) Indicates models with factory installed thermal expansion valve.

(T) Indicates models with factory installed thermal expansion valve.

MODEL

AIRFLOW

WET COIL

UPFLOW CASED "A" TYPE

G1FA024S14(T)

G1UA024S14

600

0.12

800

0.21

1000

0.33

G1FA024S17(T)

G1UA024S17

600

0.10

800

0.17

1000

0.27

G1FA030S14(T)

G1UA030S14

800

0.14

1000

0.22

1200

0.31

G1FA036S14(T)

G1UA036S14

1000

0.21

1200

0.30

1400

0.40

G1FA036S17(T)

G1UA036S17

1000

0.18

1200

0.26

1400

0.36

G1FA036S21(T)

G1UA036S21

1000

0.15

1200

0.22

1400

0.30

G1FA048S17(T)

G1UA048S17

1200

0.19

1400

0.25

1600

0.33

1800

0.42

G1FA048S21(T)

G1UA048S21

1200

0.16

1400

0.22

1600

0.28

1800

0.36

G1FA060S21(T)

G1UA060S21

1600

0.25

1800

0.32

2000

0.39

2200

0.47

G1FA060S24(T)

G1UA060S24

1600

0.22

1800

0.28

2000

0.35

2200

0.42

HORIZONTAL-DUCT TYPE

G1HD024

600

0.06

800

0.10

1000

0.16

G1HD036

1000

0.19

1200

0.28

1400

0.38

G1HD048

1200

0.14

1400

0.19

1600

0.25

1800

0.32

G1HD060

1600

0.16

1800

0.20

2000

0.25

2200

0.30

HORIZONTAL CASED

G1HA024H14 (T)

600

0.07

800

0.12

1000

0.19

G1HA036H14 (T)

800

0.21

900

0.25

1150

0.30

1200

0.31

G1HA036H17 (T)

1000

0.20

1100

0.24

1200

0.27

1300

0.30

G1HA048H21 (T)

1400

0.25

1500

0.28

1550

0.30

1600

0.33

G1HA060H24 (T)

1700

0.25

1800

0.28

1850

0.30

1900

0.31

2000

0.34

MODEL

AIRFLOW

WET COIL

CASED "A" TYPE MULTI-POSITION

G2FD024(S,H)14(T)

600

0.10

800

0.19

1000

0.29

G2FD024(S,H)17(T)

600

0.08

800

0.15

1000

0.23

G2FD035(S,H)14(T)

800

0.22

1000

0.34

1200

0.49

G2FD030(S,H)17(T)

800

0.18

1000

0.28

1200

0.40

G2FD036(S,H)17(T)

1000

0.17

1200

0.24

1400

0.33

G2FD036(S,H)21(T)

1000

0.23

1200

0.33

1400

0.45

G2FD046(S,H)17(T)

1000

0.15

1200

0.22

1400

0.30

G2FD042(S,H)21(T)

1200

0.22

1400

0.30

1600

0.40

G2FD048(S,H)21(T)

1200

0.17

1400

0.24

1600

0.31

1800

0.39

G2FD048(S,H)24(T)

1200

0.15

1400

0.21

1600

0.27

1800

0.34

G2FD060(S,H)24(T)

1600

0.22

1800

0.28

2000

0.34

2200

0.41

G2FD061H24

1600

0.18

1800

0.23

2000

0.28

2200

0.34

UNCASED UPFLOW

G1NA024S17G

600

0.11

800

0.20

1000

0.31

G1NA030S17H

800

0.17

1000

0.27

1200

0.38

G1NA030S17K

800

0.16

1000

0.25

1200

0.36

G1NA036S17J

1000

0.21

1200

0.31

1400

0.42

G1NA036S17L

1000

0.22

1200

0.30

1400

0.38

G1NA036S21C

1000

0.18

1200

0.24

1400

0.29

G1NA042S24W

1200

0.29

1400

0.39

1600

0.51

G1NA048S21D

1200

0.28

1400

0.38

1600

0.50

1800

0.63

G1NA060S24T

1600

0.25

1800

0.32

2000

0.39

2200

0.47

Advertising
This manual is related to the following products: