York R-410A User Manual

Page 20

Advertising
background image

251933-YTG-J-1009

20

Johnson Controls Unitary Products

115°F

125°F

750

77

35.1

3.4

12.9

11.4

8.5

-

-

-

31.2

3.6

10.8

9.7

7.2

-

-

-

72

31.3

3.3

18.9

16.0

13.2

10.3

-

-

27.7

3.5

17.5

14.6

11.8

9.0

-

-

67

27.5

3.2

24.9

20.7

17.9

15.0

12.1

-

24.1

3.4

24.1

19.3

16.5

13.7

10.9

-

62

25.1

3.1

25.1

25.1

20.5

17.7

14.8

11.9

22.2

3.3

22.2

22.2

18.3

15.5

12.7

9.9

900

77

36.2

3.4

16.2

12.8

9.4

-

-

-

31.9

3.7

14.9

11.3

8.0

-

-

-

72

32.3

3.3

21.4

18.0

14.6

11.3

-

-

28.3

3.6

19.8

16.5

13.2

9.9

-

-

67

28.3

3.2

26.6

23.2

19.8

16.5

13.1

-

24.7

3.4

24.7

21.7

18.4

15.1

11.8

-

62

25.8

3.2

25.8

25.8

22.8

19.4

16.1

12.7

22.8

3.3

22.8

22.8

20.4

17.1

13.8

10.5

57

26.7

3.2

26.7

26.7

23.6

20.2

16.8

13.5

24.0

3.4

24.0

24.0

20.9

17.6

14.3

11.0

1050

77

37.2

3.4

19.4

14.3

10.4

-

-

-

32.7

3.7

19.1

12.9

8.8

-

-

-

72

33.2

3.3

23.9

20.0

16.1

12.2

-

-

29.0

3.6

22.2

18.4

14.6

10.7

-

-

67

29.1

3.3

28.3

25.7

21.8

18.0

14.1

-

25.3

3.5

25.3

24.1

20.3

16.5

12.6

-

62

26.6

3.2

26.6

26.6

25.1

21.2

17.3

13.5

23.3

3.4

23.3

23.3

22.5

18.7

14.9

11.0

57

27.5

3.2

27.5

27.5

25.9

22.1

18.2

14.3

24.6

3.4

24.6

24.6

23.0

19.2

15.4

11.6

1200

77

38.3

3.4

22.7

15.7

11.3

-

-

-

33.5

3.7

23.2

14.6

9.7

-

-

-

72

34.1

3.4

26.3

21.9

17.6

13.2

-

-

29.7

3.6

24.6

20.2

15.9

11.6

-

-

67

30.0

3.3

30.0

28.2

23.8

19.4

15.1

-

25.9

3.5

25.9

25.9

22.2

17.8

13.5

-

62

27.3

3.2

27.3

27.3

27.3

23.0

18.6

14.2

23.9

3.4

23.9

23.9

23.9

20.3

15.9

11.6

57

28.3

3.2

28.3

28.3

28.3

23.9

19.5

15.1

25.2

3.4

25.2

25.2

25.2

20.9

16.5

12.2

1350

72

34.8

3.4

27.4

22.6

17.8

13.0

-

-

30.2

3.6

25.0

20.3

15.6

10.8

-

-

67

30.5

3.3

30.5

28.9

24.1

19.3

14.5

-

26.3

3.5

26.3

26.3

21.7

17.0

12.3

-

62

27.9

3.2

27.9

27.9

27.7

22.9

18.1

13.3

24.3

3.4

24.3

24.3

24.3

19.7

14.9

10.2

57

28.8

3.2

28.8

28.8

28.7

23.8

19.0

14.2

25.6

3.4

25.6

25.6

25.4

20.6

15.9

11.2

1500

72

35.4

3.4

28.5

23.3

18.0

12.8

-

-

30.6

3.6

25.5

20.3

15.2

10.1

-

-

67

31.1

3.3

31.1

29.7

24.4

19.2

14.0

-

26.7

3.5

26.7

26.4

21.3

16.2

11.0

-

62

28.4

3.2

28.4

28.4

28.1

22.8

17.6

12.4

24.6

3.4

24.6

24.6

24.2

19.1

13.9

8.8

57

29.3

3.2

29.3

29.3

29.0

23.8

18.5

13.3

26.0

3.4

26.0

26.0

25.6

20.4

15.3

10.1

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower

Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZF036 (3.0 Ton) (Continued)

Air on

Evaporator Coil

Temperature of Air on Condenser Coil

Total

Capacity

1

(MBh)

Total
Input

(kW)

2

Sensible Capacity (MBh)

Total

Capacity

1

(MBh)

Total
Input

(kW)

2

Sensible Capacity (MBh)

CFM

WB
(°F)

Return Dry Bulb (°F)

Return Dry Bulb (°F)

90

85

80

75

70

65

90

85

80

75

70

65