Technical features

Cooling only models

RTC 07 K

RTC 10 K

RTC 15 K

RTC 20 K

RTC 25 K

RTC 30 K

Cooling capacities

kW

6.90

8.90

14.00

17.90

21.80

27.00

Power input in cooling

kW

2.95

4.04

6.80

8.95

10.10

13.00

In duct outdoor side sound power level

dB(A)

71

71

69

74

76

76

In duct indoor side sound power level

dB(A)

70

71

67

73

75

75

Heat pump models

RTH 07 K

RTH 10 K

RTH 15 K

RTH 20 K

RTH 25 K

RTH 30 K

Cooling capacities

kW

6.80

9.00

14.00

18.00

20.20

27.00

Power input in cooling

kW

3.09

4.09

6.80

9.00

10.00

12.30

Heating capacities

kW

7.00

10.40

14.50

18.00

20.20

27.50

Power input in heating

kW

2.92

4.35

5.29

6.20

7.51

11.20

In duct outdoor side sound power level

dB(A)

70

80

74

74

83

81

In duct indoor side sound power level

dB(A)

65

80

73

73

83

81

Common characteristics
Power supply

230V/1/50Hz

400V/3 + N/ 50Hz

Nominal / Starting current

A

17 / 72

10.1 / 45

13 / 62

15.4 / 79

18.7 / 77

21.8 / 80

Main switch (1)

A

25

20

25

25

25

32

Main cable (1)

Nbr. x mm

2

3 x 4

5 x 2,5

5 x 4

5 x 4

5 x 4

5 x 6

Cable to standard thermostat (2)

Nbr. x mm

2

10 x 0,22

Evaporator fan at nominal airflow

Airflow

m

3

/h

1 970

2 430

4 000

4 485

5 000

5 850

Standard ESP

Pa

25

37

50

50

62

62

Condenser fan at nominal airflow

Airflow

m

3

/h

2 380

3 450

4 350

5 255

5 200

6 400

Standard ESP

Pa

50

50

50

50

50

50

Nett dimensions

Height

mm

478

555

555

585

640

640

Length

mm

1 100

1 150

1 310

1 570

1 750

1 750

Depth

mm

1 100

1 150

1 310

1 570

1 650

2 050

Nett weight

RTC

kg

154

180

214

275

345

405

Nett weight

RTH

kg

163

190

224

285

350

412

(1) For information only. These should be checked for compliance with local regulations depending also on installation and cable type

(2) Shield type cable only
All the data are at EUROVENT conditions with 230V/1/50Hz or 400V/3+N/50Hz.
Cooling : Entering indoor coil temp. 27ºC / 19ºC WB and outdoor temperature 35ºC
Heating : Entering indoor coil temp. 20ºC and outdoor temperature 7ºC / 6ºC WB

Compatibility table / Codes

Cooling only models

RTC 07 K

RTC 10 K

RTC 15 K

RTC 20 K

RTC 25 K

RTC 30 K

661210741

661211043

661211543

661212043

661212543

661213043

Heat pump models

RTH 07 K

RTH 10 K

RTH 15 K

RTH 20 K

RTH 25 K

RTH 30 K

662050741

662051043

662051543

662052053

662052543

662053043

Thermostat
Delivered as standard with the unit

DPC-1

Accessories or options

Remarks

Code

Electrical Heaters *
(in duct)

5 kW / 1ph.

611760561

A

l

5 kW / 3ph.

611760573

l

l

10 kW / 3ph.

611761033

l

l

5 kW / 3ph.

611760653

l

l

l

l

10 kW / 3ph.

611761083

l

l

l

l

15 kW / 3ph.

611761513

l

l

l

l

Low ambient regulation

613111531

O

l

l

l

613113085 *

l

l

l

Copper-copper coils unit

O

l

l

l

l

l

l

Anti-corrosion blue fin coil

O

l

l

l

l

l

l

A = Accessory (supplied loose) O = Option (factory fitted) O/A = If you want this item factory fitted, precise it in the order form. * Not protected against external conditions.

Advertising