YORK INTERNATIONAL

36

Heating Performance Data –

Gas/Electric Heat

GAS HEATING

ELECTRIC HEATING

TABLE 13 – ELECTRIC HEAT PERFORMANCE DATA

UNIT

SIZE (kW)

NOMINAL

HEAT CAPACITY

AIR FLOW MIN

MAX TEMP RISE

HEATER SIZE (kW)

(kW)

(m3/hr)

(°C)

40

40

40037

13,592

16

50-65 Ton

80

80

80075

16,990

25

108

108

108101

20,388

28

150

150

150140

23,786

34

80

80

80075

16,990

25

70-85 Ton

108

108

108101

20,388

28

150

150

150140

23,786

34

200

200

200187

25,485

42

80

80

80075

16,990

25

108

108

108101

20,388

28

90-95 Ton

150

150

150140

23,786

34

200

200

200187

25,485

42

250

250

250234

27,184

49

TABLE 12 – GAS HEAT PERFORMANCE DATA

GAS INPUT CAPACITY

MAXIMUM OUTPUT CAPACITY

AIRFLOW (m3/hr)

TEMP. RISE

UNIT

(BTU/HR X 1000)

(BTU/HR X 1000)

MIN.

MAX.

(°C)

50-65

375

300

11808

47147

10-40

750

600

18944

47147

20-50

375

300

11808

47147

10-40

70-85

750

600

18944

47147

20-50

1125

900

25740

56619

25-55

375

300

11808

47147

10-40

90-95

750

600

18944

47147

20-50

1125

900

25740

56619

25-55