York S1-33101975102 User Manual

Repair part kit installation instructions, Replacement demand defrost control board, Installation

Advertising
background image

REPLACEMENT DEMAND DEFROST CONTROL BOARD

S1-33101975102

FOR USE WITH MODELS: 12, 13 & 14 SEER HEAT PUMPS

REPAIR PART KIT INSTALLATION INSTRUCTIONS

Subject to change without notice. Printed in U.S.A.

035-21270-001-A-0906

Copyright © by York International Corp. 2006. All rights reserved.

Supersedes: Nothing

Unitary

5005

Norman

Product

York

OK

Group

Drive

73069

INSTALLATION

1.

Power off unit totally - 240V & 24V.

2.

Carefully record positions and colors of wiring removed.

3.

Remove old defrost circuit board.

4.

Install replacement circuit board - utilizing same placement,
mounting & screws.

5.

Refer to unit Installation Manual or Table 1 below - and set
the Demand Defrost Curve Selection Jumper to the proper
position. For the new jumper setting to take effect - all 24V
power to the board must be removed and reapplied.

6.

Complete the installation and power up the unit, re-apply-
ing both 240V & 24V.

DEFROST CURVE SELECTION

When the control board is replaced, the jumper MUST be
placed in a numbered position. Select the proper jumper posi-
tion from Table1. If the jumper is missing or in the P posi-
tion, the replacement control will not energize the
compressor.

When the jumper position is changed, the control will not act
upon the jumper changes until the thermostat calls are de-ener-
gized or power (24 VAC) to the control is cycled.

The control will display the active defrost curve using the X/L
terminal when the heat pump is operating in a defrost cycle that
has been forced using the TEST inputs. For instance, the X/L
output will be energized with two flashes when defrost curve 2
is active. The control only reads the jumper input when the Y
and W thermostat inputs are de-energized.

FIGURE 1: Outdoor Unit Control Box

FIGURE 2: Demand Defrost Control Module

HEATER LIMIT SWITCH

(Not on all Units)

DUAL

RUN/FAN

CAPACITOR

GROUND

LUG

CONTACTOR

DEFROST

CONTROL

BOARD

“FINGERED”

BUSHING

LOW

VOLTAGE

BOX

REVERSIBLE HIGH

VOLTAGE CONDUIT PLATE

START

CAPACITOR

(Not on all Units)

START RELAY

(Not on all Units)

TEST

AMBIENT

AMBG

COIL

G

COIL

1

2

3

4

COND

FA

N

HIGH

VOL
TAGE

PRESSURE

M

SWITCH

REV

VALVE

X/L

R

C

Y

O

W

W1/66

X/L

R

C

Y

O

W
W1/66

DEMAND

DEFROST CURVE

SELECTION JUMPER

P

TABLE 1:

Defrost Initiate Curves

Defrost Curve Selection

Jumper Position

1

2

3

4

14 Seer

2, 3, 4 Ton

2.5, 3.5 Ton

None

None

All Other Models

All

None

None

None

Advertising