York AHP18 User Manual

Page 6

Advertising
background image

255029-YTG-M-0610

6

Johnson Controls Unitary Products

PHYSICAL & ELECTRICAL DATA

Models

AHP18B**H21

AHP24B**H21

AHP30B**H21

AHP36C**H21

Blower - Diameter x Width

9 x 6

10 x 9

10 x 9

10 x 10

Motor

HP

1/3 HP

1/4 HP

1/2 HP

3/4 HP

Nominal RPM

1075

1075

1075

1075

Voltage

230

Amps

Full Load (230)

1.9

1.5

2.2

3.6

Filter

1

Type

DISPOSABLE OR PERMANENT

Size

16 x 20 x 1

16 x 20 x 1

16 x 20 x 1

20 x 20 x 1

Permanent Type Kit

1PF0601BK

1PF0601BK

1PF0601BK

1PF0602BK

Shipping / Operating Weight (lbs.) - N Models

128/122

132/126

139/133

162/156

Shipping / Operating Weight (lbs.) - H Models

131/125

135/129

142/136

165/159

Models

AHP42C**H21

AHP48D**H21

AHP60D**H21

Blower - Diameter x Width

10 x 10

10 x 10

11 x 10

Motor

HP

3/4 HP

3/4 HP

1 HP

Nominal RPM

1075

1075

1050

Voltage

230

Amps

Full Load (230)

3.8

3.8

7.6

Filter

1

Type

DISPOSABLE OR PERMANENT

Size

20 x 20 x 1

22 x 20 x 1

22 x 20 x 1

Permanent Type Kit

1PF0602BK

1PF0603BK

1PF0603BK

Shipping / Operating Weight (lbs.) - N Models

164/158

AHP - 186/175
SHP - 182/171

AHP - 189/178

SHP - 185 /174

Shipping / Operating Weight (lbs.) - H Models

167/161

190/179

193/182

1. Field Supplied.

ELECTRICAL DATA - COOLING ONLY (60 Hz)

Models

Total Motor Amps

Minimum Circuit Ampacity

Max. O.C.P.

1

Amps/Type

Minimum Wire

Size A.W.G.

60 Hertz

60 Hertz

208V

230V

208V

230V

AHP18B**H21

1.7

1.9

2.1

2.4

15

14

AHP24B**H21

1.4

1.5

1.8

1.9

15

14

AHP30B**H21

2

2.2

2.5

2.8

15

14

AHP36C**H21

3.3

3.6

4.1

4.5

15

14

AHP42C**H21

3.4

3.8

4.3

4.8

15

14

AHP48D**H21

3.4

3.8

4.3

4.8

15

14

AHP60D**H21

7.6

7.6

9.5

9.5

15

14

1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.