Sub-Menus

Configure Inv/Chg Menu (Configure Inverter/Charger Menu)

Cfg/Inv Chg is a sub-menu. If selected, the following list of sub-menu
items appears.

Max Chg Rate

Full name

Maximum charge rate

Configurable setting

The actual battery charge rate is determined by two things: the battery
bank size setting (C) divided by 5 (C÷5) and the charge rate setting (0 to
100%).

For example, if the battery bank size is set to 300 Ah (C) and the charge
rate is set at 100%, the maximum charge rate is:

300 ÷ 5 = 60 amps × 100% which is a 60 amp charge rate.

If the charge rate setting is adjusted to 50%, the maximum charge rate is:

300 ÷ 5 = 60 amps × 50% which is a 30 amp charge rate.

The RS3000 has a maximum charge rate of 150 amps. Even though you
can set a bank size of 2000 Ah, where C÷5 is 2000 ÷5 = 400 amps, the
RS3000 would still charge at 150 amp maximum.

You can adjust the Max Chg Rate settings as follows:

When to use

Displayed only if in charger mode when you wish to control the
maximum charge rate to your batteries.

Max Chg Rate

[100%]

Range of values

Increment

Default

10% to 100%

10

100%