York 110 User Manual

Fan coil unit low body, 2 & 4 pipe system), Water s ystems

Advertising
background image

W

ATER S

YSTEMS

Features

• 6 speed fan
• Cabinet factory fitted
• Valve factory fitted
• Electrical heater factory fitted
• Thermal or modulating valve
• Service valve

Dimensions indicated next page
(1) Cooling capacities based on 7ºC EWT

∆t 5ºC indoor temperature 27ºC DB / 19ºC WB - (2 pipes - high speed fan)

(2) Heating capacities based on 70ºC EWT

∆t 10ºC indoor temperature 20ºC - (2 pipes - high speed fan)

(3) In cooling mode 2 rows
For other conditions contact York international

Technical features

YLVR - YLIVR

Model

110

112

114

216

218

Cooling capacity (1) 2 rows

W

832

1054

1493

2041

2356

Cooling capacity (1) 3 rows

W

913

1266

1790

2327

2714

Heating capacity (2) 1 row

W

1167

1691

2319

3029

3552

Pressure drop (3)

kPa

7

1.7

3.8

9

11.7

Power supply

V/Ph/Hz

230 / 1 / 50 + E

Sound power level (3)

dB(A)

49

50

53

53

55

Sound pressure level at 3 m

dB(A)

31

32

35

35

37

Water connections

inch

1/2 “

Thermostats

CSL00 (Built in)
CSR00 (Wall mounted)
Fan speed selector

CML00 (Built in)
CMR00 (Wall mounted)
Thermostat with manual fan speed and S/W
change over

CEL00 (Built in)
CER00 (Wall mounted)
Thermostat with manual fan speed and automatic
change over

CEL20 (Built in)
CER20 (Wall mounted)
Thermostat with auto. fan speed and automatic
change over

CEL30 (Built in)
CER30 (Wall mounted)
Thermostat with auto. fan speed and automatic
change over for modulating valve

Fan Coil Unit

LOW BODY

(2 & 4 pipe system)

A complete range from 0.8 kW up to 2.7 kW

Selection

software

Advertising
This manual is related to the following products:

112, 216, 218, 114